Conext SW4048 4,000W 48V Installation
Table Of Contents
- Conext™ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Basic Protection Features
- Grid-interactive and Other Features
- Load Shaving
- AC Support
- Grid-Interactive Delay Feature
- AC Coupling
- AC Couple Smart Charge
- Storing the State of the Inverter Mode
- NoLoadVD
- Low Battery Cut Out Hysteresis
- LBCO Delay
- Lithium Ion Battery Type
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- AC Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Advanced Features Menu
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuring Advanced Settings
975-0638-01-03 4–33
AC In setting The Conext SW accepts only a single AC source - either from the grid or from a
generator. In a power system where the Conext SW is solely connected to the
grid and an AGS is neither present nor required, the AC In setting can be either
Gen1 or Grid1. Therefore, the default value of Gen1 need not be changed.
In a situation where the AC source is a generator and the AGS is being used to
start the generator to produce AC power, the AC In setting must be set to Gen1.
Therefore, the default value of Gen1 must remain unchanged.
In a power system where the two AC sources are available but only one AC
source can be used, an external transfer switch becomes necessary. When an
external transfer switch is used and an AGS (with a B+ signal connection) is also
present, change the AC In setting to Grid1.
Setting the Device Name
The Dev Name setting allows you to customize the name of the Conext SW as it is
displayed on other screens and menus.
The available characters are:
• A to Z
• a to z
• 0 to 9
•space
To customize the Conext SW name:
1. On the device setup menu, select Advanced Settings.
If Basic Settings appears instead of Advanced Settings on the Setup
menu, display Advanced Settings by pressing Enter + up arrow + down
arrow simultaneously.
On the Advanced Settings menu, select Multi Unit Config, and then
press Enter.
2. Select Dev Name, and then press Enter.
The last letter of the Conext SW name is highlighted.
3. Begin customizing the device name.
• To change the character, press the up or down arrow button. Holding
down the button causes the characters to scroll more quickly.
• To delete the character, press Exit.
• To add characters, press Enter.
4. When the correct character is shown, press Enter to select it.
5. After pressing Enter to select the last character of your customized device
name, press Enter again to return to the menu.
NOTE: Increasing the number of characters in a device name may cause other
text on the same line to run off the edge of the screen. Device names should be
limited to 10 characters or less.