Conext SW4048 4,000W 48V Installation
Table Of Contents
- Conext™ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0638-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Introduction
- Materials List
- Key Features
- Key Features Explained
- Basic Protection Features
- Grid-interactive and Other Features
- Load Shaving
- AC Support
- Grid-Interactive Delay Feature
- AC Coupling
- AC Couple Smart Charge
- Storing the State of the Inverter Mode
- NoLoadVD
- Low Battery Cut Out Hysteresis
- LBCO Delay
- Lithium Ion Battery Type
- Components and Mechanical Features
- System Components
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Conext SW Inverter/Charger Mechanical Features
- Conext SW Front and Side Panels
- Operation
- Start Up Behavior
- Inverter Operation Using the Front Panel
- Operating Limits for Inverter Operation
- Operating Limits for Charger Operation
- Inverter/Charger Operation using the System Control Panel (SCP)
- SCP Features
- Using the Standby Button
- SCP Navigation
- Changing Operational Settings
- Configuration via SCP
- Viewing the Firmware Revision Number
- Setting the Time and Date
- Viewing the Basic and Advanced Settings Menus
- Configuring Basic Settings
- Configuring Advanced Settings
- Inverter Settings Menu
- Charger Settings Menu
- AC Settings
- AC Support Settings
- Multi Unit Config Menu
- Restoring Factory Default Settings
- Advanced Features Menu
- Configuration Sheet
- Troubleshooting
- General Troubleshooting Guidelines
- Inverter Applications
- View Device Info Logs
- Troubleshooting the Conext SW via the SCP
- Fault Detection Types
- Warning Types
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
Configuration via SCP
4–34 975-0638-01-03
Setting the Device Number
Setting the device number gives a Xanbus-enabled device a unique identity
when several devices of the same type are installed in the networked power
system. When each identical device has a unique number, the SCP can correctly
identify and display status information for each device. A device number consists
of two digits ranging from 00 (default) to 31.
If only one of each device is installed in the networked power system, you do not
need to set the device number. However, setting the device number to a value
other than 00 is recommended in case you need to use the Restore Defaults
command. After performing the command, checking that the device number has
returned to 00 indicates that the command was successfully completed.
To set the Conext SW device number:
1. On the Conext SW Setup menu, select Advanced Settings.
If Basic Settings appears instead of Advanced Settings on the Setup
menu, display Advanced Settings by pressing Enter + up arrow + down
arrow simultaneously.
On the Advanced Settings menu, select Multi Unit Config, and then
press Enter.
2. On the Multi Unit Config menu, select Dev Number. See Figure 4-11.
3. Press Enter to highlight the instance number.
4. Use the up and down arrow buttons to adjust the two-digit identifier number.
5. Press Enter.
Figure 4-11 Setting a Device Number
CSW4024 01: Multi
Dev Name
Dev Number
Invtr Mode
Battery
[CSW4024]
[01]
[Slave]
[HouseBatt1]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.