Configuration via SCP
4–38 975-0638-01-03
Configuration Sheet
SETTING DESCRIPTION
DEFAULT
24-volt
DEFAULT
48-volt
YOUR
SETTING
Inverter
Settings
Low Batt Cut Out
Select battery voltage below which batteries will be cut out
21.0V 42.0V
LBCO Delay
Select the time delay before low battery cut out is engaged
10sec 10sec
Hi Batt Cut Out
Select the voltage above which batteries will be cut out
29.0V 58.0V
Search Watts
Select Watts at which level Search Mode triggers on
50W 50W
Search Delay
Select delay time before Search Mode triggers on
2sec 2sec
Inv Block Start
Sets the time to halt inverting
12:00AM 12:00AM
Inv Block Stop
Sets the time to resume inverting
12:00AM 12:00AM
Charger
Settings
Batt Type
Select your battery type (FLOODED, GEL, AGM, Custom)
Flooded Flooded
Custom Settings
Makes BATTERY CUSTOM SETTINGS screen visible
-- --
Eqlz Support
Enable battery EQUALIZE function
Enabled Enabled
Eqlz Voltage
Select maximum EQUALIZE voltage
32.0V 62.0V
Bulk Voltage
Select maximum BULK charge voltage
28.8V 57.6V
Bulk Termination
Voltage
Select maximum BULK TERMINATION charge voltage
28.4V 56.8V
Absorb Voltage
Select maximum ABSORPTION charge voltage
28.8V 57.6V
Float Voltage
Select maximum FLOAT charge voltage
27.0V 54.0V
Batt Temp Comp
Select BATTERY TEMPERATURE COMP coefficient
-54mV/C -108mV/C
Batt Capacity
Select battery bank capacity
250Ah 250Ah
Max Chg Rate
Select maximum charge rate
100% 100%
Charge Cycle
Select 2 or 3 stage charge cycle
3Stage 3Stage
Default Batt Temp
Select system default battery temp setting
Warm Warm
ReCharge Volts
Select voltage at which charger will initiate a charge cycle
25.0V 50.0V
Absorb Time
Sets the maximum Absorption time
180min 180min
Auto Chg Enable
Select automatic charging, overrides Charger setup
Disabled Disabled
Chg Block Start
Sets the time to halt charging
12:00AM 12:00AM
Chg Block Stop
Sets the time to resume charging
12:00AM 12:00AM
AC
Settings
AC Breaker
Select AC Input current limit
30A 30A
AC Lo Volt
Select lowest acceptable AC voltage
95V 95V
AC Hi Volt
Select highest acceptable AC voltage
135V 135V
AC Lo Freq
Select lowest acceptable AC frequency
55Hz 55Hz
AC Hi Freq
Select highest acceptable AC frequency
65Hz 65Hz
AC
Support
AC Supp Mode
Sets the AC Support feature
Enabled Enabled
AC Supp Volts
Sets the AC support voltage
26.5V 53.0V
Load Shave
Sets the load shaving feature
Disabled Disabled
Load Shave Amps
Sets the current for load shaving
24A 24A
Load Shave Start
Sets the start time for load shaving
12:00AM 12:00AM
Load Shave Stop
Sets the stop time for load shaving
12:00AM 12:00AM
AC Supp on Soc
Sets the AC Support feature based on SOC
Enabled Enabled
AC Supp Start Soc
Sets the start time for SOC AC support
80% 80%
AC Supp Stop Soc
Sets the stop time for SOC AC support
50% 50%