Installation Manual

Wiring the Conext XW+ and Conext XW+ PDP
3–60 975-0239-01-01 Rev J
This manual is for use by qualified personnel only
Breaker Installation
1. Remove all connections to the utility grid, generator, inverter load sub-panel,
and Conext XW+ Inverter/Charger.
2. Remove the pre-installed breakers from the PDP, and mount the 3-pole, 60 A,
120/208 VAC breakers (included in the Conext 3 Phase Breaker Kit) onto the
DIN rail.