Installation Manual

Electrical Specifications
975-0239-01-01 A–3
This manual is for use by qualified personnel only
Grid-tie Specifications
DC Current at Rated Continuous Power
(Inverter Mode)
180 A 150 A
Continuous Charge Rate at L-L voltage
(Charger Mode)
140 A 110 A
Power Factor Corrected Charging PF (0.98)
Typical Transfer Time 8 ms
a.Conext XW+ 6848 NA (Part Number 865-6848-01)
b.Conext XW+ 5548 NA (Part Number 865-5548-01)
Note: Specifications are subject to change without prior notice.
Function 120 V/240 V 120 V Response Time
Anti-islanding reconnect 254.4 V (± 3 V) 127.2 V (± 3 V) 300 s (+1/–0 s)
Over frequency disconnect 60.5 Hz (± 0.05 Hz) 60.5 Hz (± 0.05 Hz) 60 ms (± 20 ms)
Under frequency disconnect 59.3 Hz (± 0.05 Hz) 59.3 V (± 0.05 Hz) 60 ms (± 20 ms)
Over voltage LN fast disconnect 135 V (± 1.5 V) 135 V (± 1.5 V) 60 ms (± 25 ms)
Over voltage LN slow disconnect 132 V (± 1.5 V) 132 V (± 1.5 V) 500 ms (± 50 ms)
Over voltage L1/L2 fast disconnect 270 V (± 3 V) 60 ms (± 25 ms)
Over voltage L1/L2 slow disconnect 264 V (± 3 V) 500 ms (± 50 ms)
Under voltage LN fast disconnect 67 V (± 5 V) 75 V (± 5 V) 60 ms (± 25 ms)
Under voltage LN slow disconnect 105.6 V (± 1.5 V) 105.6 V (± 1.5 V) 1000 ms (± 40 ms)
Under voltage L1/L2 slow disconnect 211.2 V (± 3 V) 100 ms (± 40 ms)
Under voltage L1/L2 fast disconnect 150 V (± 10 V) 60 ms (± 25 ms)
Table A -1 Conext XW+ Inverter/Charger Electrical Specifications
Conext XW+ 6848 NA Conext XW+ 5548 NA
XW-NA-Install.book Page 3 Wednesday, August 12, 2015 2:23 PM