Output Power Versus Ambient Temperature
When the internal temperature of the Conext XW+ exceeds a preset limit, it
begins to limit output power automatically to stop maximum internal temperatures
from being exceeded.
Note: For the Conext XW+ 6848 model, the power can be limited by the
installed DC and AC breakers. For example, at 8500 W the DC or AC breakers
may disconnect before the 30 minute rating.
Figure A-2 Output Power Versus Ambient Temperature
0
1000
2000
3000
4000
5000
6000
7000
8000
-25 -15 -5 5 15 25 35 45 55 65 75
XW+ Series Power derating
XW+ 6848
XW+ 5548
Output Power (Watts)
Ambient Temperature (°C)