Installation Manual

Specifications
A–12 975-0239-01-01
This manual is for use by qualified personnel only
Mechanical Specifications
Note: Specifications are subject to change without prior notice.
Table A -2 Conext XW+ Inverter/Charger Mechanical Specifications
Model Conext XW+ 6848 NA Conext XW+ 5548 NA
Supported Battery Types Flooded (default), Gel, AGM, Lithium Ion, Custom
Battery bank size 440–10000 Ah
Non-Volatile Memory Yes
Inverter Information Panel
Status LEDs indicate AC In status, faults/warnings, equalize
mode, battery level. 3-character display indicates output power or
charge current, fault/warning codes.
STARTUP
/
SHUTDOWN
and
equalize button
Multiple Unit Configurations
Clusters of up to 3 parallel units in 120/240 three-wire, single-
phase configuration. Up to 4 clusters possible using multi-cluster
for a total of 12 units when using an external AC contactor.
System Network
Conext Xanbus™ (publish-subscribe network, no need for hubs
or special cards)
Emissions FCC Part 15, Class B Industry Canada ICES-003 Issue 5,
Class B
Regulatory approvals CSA C22.2 No. 107.1-01 - General Use Power Supplies
UL 1741 - 2nd Ed - Inverters, Converters, Controllers and
Interconnection System Equipment
Enclosure Type NEMA Type 1—Indoor
Rated Temperature Range
(meets specifications)
32–77 °F (0–25 °C)
Operational Temperature Range -13–158 °F (-25–70 °C)
Storage Temperature Range -40–185 °F (-40–85 °C)
Inverter Dimensions (H × W × D)
23 × 16 × 9" (580 × 410 × 230 mm)
Shipping Dimensions (H × W × D)
28 × 22 ½ × 15 ½” (711 × 572 × 394 mm)
Inverter Weight 125 lb (57 kg) 115 lb (52 kg)
Shipping Weight 132 lb (60 kg) 122 lb (55 kg)
XW-NA-Install.book Page 12 Wednesday, August 12, 2015 2:23 PM