Installation Manual

Converting 120 V/240 V Split-Phase to 120 V Single-Phase
975-0239-01-01 Rev J C–7
This manual is for use by qualified personnel only
Reconfiguring the Secondary Transformer Wires on X1 and X2 Connec-
tors
To reconfigure the secondary transformer wires on the X1 and X2 connectors:
1. Locate the X1 and X2 connectors (see Figure C-3).
2. Remove the secondary transformer wire X2 (black) from slot X2-A, and then
insert it into slot X2-B (see Figure C-4 and Figure C-5).
3. Remove the secondary transformer wire X3 (white) from slot X3-A, and then
insert it into slot X3-B (see Figure C-4 and Figure C-5).
4. Insert one small jumper between slot X2-A and X2-B (see Figure C-4 and
Figure C-5). Insert jumper on top of the wire.
5. Tighten all terminals to 35 in-lb (4.0 N-m) per the torque information printed
on the AC board. See Figure C-3 for the torque information location.