Installation Manual

Converting 120 V/240 V Split-Phase to 120 V Single-Phase
975-0239-01-01 Rev J C–9
This manual is for use by qualified personnel only
Reconfiguring the AC Ports on the Load, AC1, and AC2 Connectors
To reconfigure the AC ports on the Load, AC1 (Grid), and AC2 (Gen)
connectors:
1. Locate the Load, AC1 (Grid), and AC2 (Gen) connectors (see Figure C-3 on
page C–7).
2. Insert one large jumper in each connector to short out N and L2, as shown in
Figure C-6.
3. Connect the AC cables as shown in Figure C-6. Insert jumper on top of the
wire.
4. Tighten all terminals per the torque information printed on the AC board.
See Figure C-3 on page C–7 for the torque information location.
5. Reconnect the DC sources (for example, batteries) by turning on the
DC breaker.
Figure C-6 Jumper Locations and AC Cable Configuration on AC Ports
Load
AC1 (Grid) AC2 (Gen)
XW-NA-Install.book Page 9 Wednesday, August 12, 2015 2:23 PM