Installation Manual

Pre-Installation and Wall-Mounting
2–12 975-0239-01-01 Rev J
This manual is for use by qualified personnel only
Communications Network Preparation
To separate the communications cables and signal cables from the DC and AC
wiring, a raceway (wire barrier) has been included in the design of both the
Conext XW+ Power Distribution Panel and the Conext XW+ Conduit Box.
This raceway is built into the bottom of the Conext XW+ Power Distribution Panel
and Conext XW+ Conduit Box (see Figure 2-11, below) and is held in place by a
single screw at the top of each raceway.
Before making AC and DC connections, route communication cables (including
Battery Temperature Sensor) through the raceways. For easier identification, use
a different color for each communications cable, or cable tags.
Connect communications cables to their components after AC and DC
connections are made.
WARNING
XANBUS SHOCK HAZARD
Xanbus cables in contact with DC or AC power can transmit an electric shock.
Do not route the Xanbus cables in the same conduit or panel as the AC and
DC power cabling.
Failure to follow these instructions can result in death or serious injury.
Figure 2-11 Example of raceways in a single-inverter system
XW-NA-Install.book Page 12 Wednesday, August 12, 2015 2:23 PM