Installation Manual

Wiring the Conext XW+ and Conext XW+ PDP
3–14 975-0239-01-01 Rev J
This manual is for use by qualified personnel only
To connect the Conext XW+ Power Distribution Panel (PDP) to the Conext
XW+ Inverter/Charger:
1. Connect the positive battery cable (pre-installed in the PDP) to the positive
battery terminal at the bottom of the Conext XW+, as shown in Figure 3-9 on
page 3–16.
2. Connect the negative battery cable (pre-installed in the PDP) to the negative
battery terminal at the bottom of the Conext XW+ Inverter/Charger.
3. Attach the DC terminal covers (included with the Conext XW+ Inverter/
Charger) to the bottom of the Conext XW+ DC terminals.
Figure 3-7 Battery terminals (bottom of Conext XW+)
Figure 3-8 Battery cable connection
Positive (+)
Battery terminal
(Red)
Negative (–)
Battery terminal
(Black)
Terminal surface
Battery cable lug
Flat washer
Split-ring washer
3/8-15 x 5/8” bolt
(included)
Copper compression lug
Note: When making the connections, be sure to observe correct hardware
stacking and proper polarity, and ensure that nothing obstructs the connection
between the terminal surface and the battery cable lug. (See Figure 3-8 on page
3–14.)
XW-NA-Install.book Page 14 Wednesday, August 12, 2015 2:23 PM