Installation Manual

Wiring the Conext XW+ Inverter/Charger with a PDP
975-0239-01-01 Rev J 3–15
This manual is for use by qualified personnel only
To connect the Conext XW+ Power Distribution Panel (PDP) to the Battery
Bank:
1. Connect your battery cables (not included) to the PDP. Connect the negative
battery cable to the DC Negative Bus, and the positive battery cable to the
input end of the GJ250A 160 VDC, 3/8" stud DC breaker (pre-installed in the
PDP), as shown in Figure 3-9 on page 3–16.
2. Route your battery cables from the PDP, through your preferred conduit path,
to the battery location. Do not connect the cables to the battery yet.
Note: To properly attach and torque the positive cable to the DC breaker, you
may need to temporarily remove the breaker from the rail.
Note: Before connecting the DC cables from the PDP to the battery, perform the
procedures in “Making AC Connections” on page 3–17.
XW-NA-Install.book Page 15 Wednesday, August 12, 2015 2:23 PM