Installation Manual

Basic Functional Test – Single Inverter
975-0239-01-01 Rev J 3–31
This manual is for use by qualified personnel only
Enabling the Inverter
Invert mode is enabled by default, and the Conext XW+ should begin inverting
upon transitioning from standby mode. If invert mode is disabled, the inverter
information panel will display "
" once out of standby mode, as shown in
Figure 3-17. If the Conext XW+ powers up in standby mode, press the S
TARTUP/
S
HUTDOWN button momentarily to change the mode from standby to operating.
To enable the inverter:
On the inverter information panel, simultaneously press the STARTUP/
S
HUTDOWN button and the Equalize button. The Conext XW+ is now enabled,
and
 (enabled) is briefly displayed on the inverter information panel, as
shown in Figure 3-18.
Figure 3-17 Disabled mode
Equalize button STARTUP/SHUTDOWN button
Figure 3-18 Enabled mode
Equalize button STARTUP/SHUTDOWN button
XW-NA-Install.book Page 31 Wednesday, August 12, 2015 2:23 PM