Installation Manual

Wiring the Conext XW+ and Conext XW+ PDP
3–32 975-0239-01-01 Rev J
This manual is for use by qualified personnel only
To disable the inverter:
On the inverter information panel, simultaneously press the STARTUP/
S
HUTDOWN button and the Equalize button. The Conext XW+ is now disabled,
and
 (disabled) is briefly displayed on the inverter information panel,
followed by "
" (as shown in Figure 3-19).
3. Monitor the invert (green kW) LED to confirm which mode the inverter is in:
•kW LED OFF – Invert mode is disabled. The inverter/charger is not
powering the AC loads. However, if good AC is present, it is passed
through to the loads.
 displayed on the inverter information panel – The inverter/charger is
in search mode and is looking for an AC load greater than the Search
Watts setting (default = 25 watts). The display shows
 (Search)
when this mode has been enabled.
LED ON – The inverter/charger is on. The inverter is operating and is
able to provide power to the AC loads. This is the default mode on initial
power-up once the unit is taken out of standby mode.
If the inverter is not operating or the inverter LED (kW) does not turn on, check all
connections. Check the inverter’s DC voltage and polarity on the positive (+) and
negative (–) terminals. Check the Fault LED. If the fault LED is on, check for a fault
code on the information panel. Correct the reported fault and clear the fault by
acknowledging it. If the DC voltage is low, then the battery bank needs to be
charged externally. Charge the battery bank and restart the functional test.