Installation Manual

Wiring the Conext XW+ and Conext XW+ PDP
3–42 975-0239-01-01 Rev J
This manual is for use by qualified personnel only
5. Attach the four, four-tab jumpers (included in the Conext XW+ Connection Kit
for INV2 INV3 PDP) to top and bottom of AC breakers as shown in Figure
3-24.
AC Wiring for a Dual-Inverter System
1. Connect the grid wiring and inverter load sub-panel wiring to the new
jumpers as shown in Figure 3-25 on page 3–43.
2. Connect INV1 LOAD (INV1 L1-LOAD, INV1 L2-LOAD), INV2 LOAD (INV2
L1-LOAD, INV2 L2-LOAD), and INV2 GRID (INV2 L1-GRID, INV2 L2-GRID)
wires to AC breakers as shown in Figure 3-25 on page 3–43.
3. Connect neutral (INV2 N-LOAD) and ground (INV2 GROUND) wiring as
shown in Figure 3-25 on page 3–43.
4. Remove the knockouts on the upper faceplate of the PDP to accommodate
additional breakers.
5. Re-label the AC breakers with the appropriate labels, included with the
Conext XW+ Power Distribution Panel.
6. Install the custom designed bypass interlock plate, as shown in Figure 3-26
on page 3–44.
Figure 3-24 Dual Inverter AC Breaker Arrangement with Multiple AC Input Sources
Note: If a backup generator or other secondary AC source is installed in the
system, reuse two of the dual-tab jumpers previously installed on INV1 Grid/
Bypass breakers for generator breakers.
1
2
7
65 98
3
4
From main AC distribution panel
IMPORTANT: Install L1 PDB in first
Grid breaker slot facing FRONT.
Failure to do so will result in overlap
of terminals on L1 and L2 PDBs and
potential for shorting to occur.
From AC Load on INV1
From AC Load on INV2
From generator disconnect
IMPORTANT: Install L1 PDB in first
Gen breaker slot facing REAR.
To AC1 on INV1
To AC1on INV2
To inverter AC distribution panel
IMPORTANT: Install L1 PDB in first
Bypass breaker slot facing REAR.
To AC2 on INV1
To AC2 on INV2
1. From main utility panel
NOTE: Install L1 power distribution
2. From AC Load on INV1
3. From AC Load on INV2
4. From generator disconnect
NOTE: Install L1 jumper in first
Gen breaker slot facing REAR.
5. To AC1 on INV1
6. To AC1 on INV2
7. To inverter load sub-panel
NOTE: Install L1 jumper in first
Bypass breaker slot facing REAR.
8. To AC2 on INV1
9. To AC2 on INV2
bar (jumper) in first Grid breaker slot
facing FRONT.
INV1 IN INV2 IN INV1 IN
INV2 IN
INV1 OUT INV2 OUTGRID GRID
(GRID) (GRID) BYPASS BYPASS AC LOADS AC LOADS GEN GEN
XW-NA-Install.book Page 42 Wednesday, August 12, 2015 2:23 PM