Installation Manual

Wiring Additional Conext XW+ units with a PDP
975-0239-01-01 Rev J 3–49
This manual is for use by qualified personnel only
5. If the installation includes a second AC source, connect L1 and L2 AC wiring
from the Generator (or other source) disconnect to the Gen breaker jumpers.
6. Connect L1 and L2 AC wiring from the Utility Grid distribution panel to the
Grid breaker jumpers.
7. Connect the neutral wiring from INV1, INV2, and INV3 to the neutral bus bar
in the PDP.
8. Connect the ground wiring from INV1, INV2, and INV3 to the ground bus bar
in the PDP.
9. Re-label the AC breakers with the appropriate labels, included with the
Conext XW+ Power Distribution Panel.
10. Install the custom designed bypass interlock plate, as shown in Figure 3-26
on page 3–44.
Figure 3-28 Triple-Inverter AC Breaker Arrangement with a Single AC Input Source
1
2
7
8
3 4
5 6
1. From AC source disconnect or
transfer switch
NOTE: Install L1 power distribution
bar (jumper) in first GRID/GEN break-
er slot facing FRONT.
2. From AC Load on INV1
3. From AC Load on INV2
4. From AC Load on INV3
5. To AC1 or AC2 on INV1
6. To AC1 or AC2 on INV2
7. To AC1 or AC2 on INV3
8. To Inverter main utility panel or
transfer switch
NOTE: Install L1 jumper in first By-
pass breaker slot facing REAR
INV1 IN INV2 IN INV3 IN INV1 OUT INV2 OUT INV3 OUT
GRID
or GEN
GRID
or GEN
GRID
or GEN
AC LOADS AC LOADS AC LOADS