If the cable is installed over an obstruction, clip the cable on both sides, as close to the obstruction
as possible.
Do not install the cable directly in front of an air conditioner. Allow a minimum of 6 feet (1.83m)
between the unit and the cable. If the SC cable is too close to the air conditioning unit’s air stream,
the moisture from the humidifier may cause false leak readings. If the cable must be installed in
front of an air conditioning unit, place the J-clips 12 to 18 inches (.305m to .457m)apart.
3-2.2 Recommended Cable Installation
Figure 3-2: Cable Installation Methods
NOTE
:
It is important to finish the end of the SeaHawk Leak Detection Cable (SC) with the
end-of-line terminator (EOL). If the EOL terminator is not present, a cable fault will
register. Note any variances between the cable layout diagram and the actual cable
installation. Wait approximately one minute. No alarm should be present.