Home Security System User Manual

User Guide: LDRA6 Chapter 4: Start-Up
15 970 484-6510 www.rletech.com
4-3.10 t – Toggle Modbus Trace On/Off
t will toggle Modbus tracing with packet viewing from the RS485 port over the RS232 port. This is a
command for advanced diagnostic purposes only.
4-3.11 z – Display Leak Zone Readings
z will display the present Leak Detection Cable readings. The Leak Zone table will display the reading for
each leg of cable and the present leakage current reading for each zone.
4-3.12 sr – summary relay mode
sr will display the current configuration of the summary relay. You can select the summary relay to either
change state on leak/fault or just a fault condition. Enter, sr <space> summary for notification on a
leak/fault condition. Enter, sr <space> fault for notification on a fault condition.
4-3.13 zr – zone relay mode
zr will display the current configuration of the zone relays. You can select the zone relays to either change
state on leak/fault (summary) or just a leak condition. Enter, zr <space> summary for notification on a
leak/fault condition. Enter, zr <space> leak for notification on a leak condition.
4-3.14 x – Exit to Bootloader
x will exit the application code and only the bootloader will be running.
zr
zr/summary (summary/leak)
zr leak
zr/leak (summary/leak)
sr
sr/summary (summary/fault)
sr fault
sr/fault (summary/fault)
Z1: Leg1: 0 Leg2: 0 Leakage: 0
Z2: Leg1: 0 Leg2: 0 Leakage: 0
Z3: Leg1: 0 Leg2: 0 Leakage: 0
Z4: Leg1: 0 Leg2: 0 Leakage: 0
Z5: Leg1: 0 Leg2: 0 Leakage: 0
Z6: Leg1: 0 Leg2: 0 Leakage: 0