Service manual

2-11
AY-ZP35PR
1.24. Self Clean operation
Heating or Fan operation and Cluster operation are performed
simultaneously.
The judgment of whether Heating or Fan operation is used is
based on the outside air temperature at 3 minutes after the start
of internal cleaning.
The operation stops after 40 minutes.

positions.
It turns to the lower direction and stays for 30 minutes.
Next moves upward and stays for 10 minutes.
Heating operation Fan operation
24
O
C
Outside air temperature
1.25. Plasmacluster Ion function
Operating the Plasmacluster Ion button while the air conditioner is
in operation or in non-operation allows the switching of the op-

“Stop”.

and (-)ions from the cluster unit to provide clean air.
If the Plasmacluster Ion generation function is operated together
with the air conditioner operation, the indoor unit fan speed and
louver direction are in accordance with the air conditioner set-
tings.
If the Plasmacluster Ion generation function is used without oper-
ating the air conditioning function, the indoor unit fan operates at
a very low speed and the upper louver is angled upward and the

can be changed by using the remote control.)
1.26. 10°C OPERATION
Heating operation with 10°C set temperature will be performed.
1)Press the MODE button of Remote controller and select HEAT
mode.
2)Press the ON / OFF button to start HEAT operation.
3)Press the 10°C button.

TO CANCEL
Press the 10°C button again.

is changed, or when the unit is turned off.
NOTE:
-
matically selected by AUTO mode.
1.27. Hot keep
If the room temperature is in the Hot keep zone during heating,
the compressor is turned off to prevent overheating.
ZONE COMPRESSOR FAN
Hot keep (When
room temperature
reaches setting
temperature)
OFF Ultra soft (Lower
than Fan speed
“soft”)
0.6
O
C
Set temperature
Hot keep zone
1.28. Winter cool
Cooling operation is available during the winter season by the
built in winter cool function.
Lower limit of outdoor temperature range is -10°C DB.
When the outside air temperature is low, the outdoor unit fan
operates at slower speed.
NOTE:
Built-in protect device may work when outdoor temperature falls
below 21°C DB., depending on conditions.
1.29. Auto restart
When power failure occurs, after power is recovered, the unit will
automatically restart in the same setting which were active before
the power failure.
1.29.1 Operating mode (Cool, Heat, Dry)








1.29.2 Setting not memorized



1.30 Heat only mode.
When heat only mode, cut the JPW jumper
cool heat mode JPW connected
heat only mode
JPW cut
JPW