Service manual

25
AF-R100CX
AF-R120CX
HEAT GAIN FROM QUANTITY
FACTORS
DAY
BTU/Hr
(Quantity
x Factor)
1. WINDOWS: Heat gain from sun.
Southeast
Northeast
South
Southwest
Southeast
West
Northwest
North
sq ft
sq ft
sq ft
sq ft
sq ft
sq ft
sq ft
No
Shades
Inside
Shades
Outside
Shades
(Area a
Factor)
60
80
75
75
110
150
120
0
25
40
30
35
45
65
50
0
20
25
20
20
30
45
35
0
Use
only
the
largest
load
Use
only
only
These factors are for single glass only. For glass block, multiply the above factors
by 0.5: for double-glass or storm windows, multiply the above factors by 0.8.
2. WINDOWS: Heat gain by conduction.
(Total of all windows)
Single glass
Double glass or glass block
sq ft
sq ft
sq ft
sq ft
sq ft
sq ft
sq ft
sq ft
ft
ft
ft
ft
watts
30
60
30
19
12
20
30
14
7
8
3
3
3
5
600
300
Light Construction Heavy Construction
x x x x x x x x x x
(Item 9) x (Factor from Map) =
3. WALLS: (Based on linear feet of wall.)
4. ROOF OR CEILING: (Use one only.)
5. FLOOR: (Disregard if floor is directly
on ground or over basement.)
6. NUMBER OF PEOPLE:
7. LIGHTS AND ELECTRICAL
EQUIPMENT IN USE
8. DOORS AND ARCHES
CONTINUOUSLY OPENED TO
UNCONDITIONED SPACE:
(Linear feet of width.)
9. SUB-TOTAL
10. TOTAL COOLING LOAD:
(BTU per hour to be used for selection
of room air conditioner(s).)
a. Outside walls
Noth exposure
Other than North exposure
b. Inside Walls (between conditioned
and unconditioned spaces only)
a. Roof, uninsulated
b. Roof, 1 inch or more insulation
c. Ceiling, occupied space above.
d. Ceiling, insulated with attic space
above
e. Ceiling, uninsulated, with attic space
above
FARGO
EUGENE
RENO
SACRAMENT
FRESNO
LAS VEGAS
PHOENIX
PUEBLO
WICHITA
SAN ANTONIO
GREEN BAY
BIRMINGHAM
ATLANTA
COLUMBIA
ROCHESTER
ALBANY
NEW HAVEN