Installation Prerequisites
3.4 Safety gear
Wear the following safety gear when dealing with the battery pack. Installers must
meet the relevant requirements onternational standards, such as IEC 60364 or the
domestic legislation.
Insulated gloves Safety goggles Safety shoes
3.5 Making network cable
Use this method to make a network cable, which is to be connected betweenthe battery
pack and the inverter or the RESU Plus.
1. Cut network cable to the needed length.
2. Strip 2.5 to 5 cm of the outer sheath at one end of the cable.
3. Untwist and separate each pair of wires.
4. Arrange the wires in this order:
1) White with an orange stripe
2) Orange
3) White with a green stripe
4) Blue
5) White with a blue stripe
6) Green
7) White with a brown stripe
18