RESU 3.3, 6.5, 10, RESU Plus

Table Of Contents
6 Conguration Switches
The RESU battery pack and RESU Plus have inside DIP switches and rotary switches,
which must be set correctly for proper communication with the inverter.
6.1 Conguring Battery pack
Remove the switch cover by pulling it up to expose the circuit board.
ON
O
FF
Switch number Type Label Default
1 DIP SW select 0000
2
2 DIP Cell select 00
2
3 Rotary CAN_H 4
4 Rotary CAN_L 5
5 Rotary GND 2
6 DIP Term Res 11
2
6.1.1 Setting for communication interface
Only one battery pack is installed, set the SW select DIP switch to 0011
2
.
Otherwise, if two are installed, set it to 0010
2
. This switch is initially set to
0000
2
.
NOTE
To be more precise, when a RESU battery pack is directly connected to an inverter,
the SW select DIP switch must be set to 0011
2
. When two battery packs are in-
39