Installation Guide

INSTALLATION
All suboors and suboor systems must be structurally sound and must be installed following their manufacturer's recommendations. Local building
codes may only establish minimum requirements of the ooring system and may not provide adequate rigidity and support for proper installation and
performance of a hardwood oor. Whenever possible install the planks perpendicular to the oor joists for maximum stability. Our warranties DO NOT
cover any problems caused by inadequate substructures or improper installation of said substructures.
Test wood suboors and wood ooring for moisture content using a pin-type moisture meter. Take readings of the suboor – minimum of 20 readings
per 1000 sq. ft. and average the results. In most regions, a “dry” suboor that is ready to work on has a moisture content of 12% or less and the wood
should be within 4% of the suboor moisture content.
ASTM F-2170 – in-situ relative humidity 85% RH or less is acceptable.
ASTM 1869 – 5.0 lbs. or less is acceptable.
Readings greater than 85% RH or 5.0 lbs. requires the use of a proper vapor retarder or adhesive/moisture abatement system.
Before moisture testing begins, the slab must be cured for a minimum of 30 days.
Basements and crawl spaces must be dry. Use of a 6 mil black polyethylene is required to cover 100% of the
crawl space earth. Crawl space clearance from ground to underside of joist to be no less than 18” and
perimeter vent spacing should be equal to 1.5% of the total square footage of the crawl space area to provide
cross ventilation. Where necessary, local regulations prevail.
The suboor must be at, meeting a minimum of 3/16 within 10’ or 1/8” in 6’.
Concrete/Wood suboors - Grind high spots or use of gypsum based patching and/or
leveling compounds which contain Portland or high alumina cement and meet or exceed
the compressive strength of 3,000 psi are acceptable. Follow the leveling compound manufacturer’s instruction.
Leveling compounds must be allowed to thoroughly cure and dry prior to installation of wood ooring.
All wet” work i.e. paint, drywall, concrete, masonry, plumbing must be complete and dry well in advance of delivery of hardwood ooring
Gutters and downspouts should be in place and the exterior grade complete to allow for proper drainage of water away from the building’s exterior
perimeter.
Flooring should not be exposed to extremes of humidity or moisture.
Permanent HVAC should be on and operational a minimum of 5 days and maintained between 65 75 degrees and a relative humidity of 35%- 55% prior
to delivery, during, and after installation of the ooring.
If HVAC is not possible at time of installation the environmental conditions must be at or near normal living conditions between 60 – 80 degrees and at
the average yearly relative humidity for the area.
It is the Installer/Owner responsibility to ensure that the conditions are acceptable prior to the installation of the hardwood
oors.
The manufacturer declines any and all problems with the hardwood ooring that are related to or attributed to improper
jobsite conditions.
RECOMMENDED SUBFLOOR SURFACES
Concrete Suboor Guidelines
Concrete slabs should be of high compressive strength and constructed to prevent groundwater from permeating the
concrete. Engineered hardwood ooring can be installed on, above, or below-grade. In addition, it can be installed over
above-ground, suspended concrete oors. The suspended concrete must be a minimum of 1 1/2 inches thick and must be
structurally sound. The exception to this is lightweight concrete (which usually contains high amounts of gypsum) having a
density of 100 pounds or less per cubic foot. Test for lightweight concrete by using a nail to scratch the surface of the
concrete. If the concrete crumbles or turns to powder, it is not sound and you should NOT install the hardwood ooring.
Wood Suboors Guidelines
Suboor panels should conform to U.S. Voluntary Product Standard PS1-07, Construction and Industrial Plywood and/or US
Voluntary PS 2-04 and/or Canadian performance standard CAN/CSA 0325.0-92 Construction Sheathing. Other CSA standards
also apply.
Acceptable Panel Suboors: Truss/joist spacing will determine the minimum acceptable thickness of the panel
subooring.
On truss/joist spacing of 16” o/c or less the industry standard for single panel subooring is minimum 5/8” 19/32”, 15.1 mm) CD Exposure 1 suboor panels,
4x8 sheets.
On truss/joist spacing of more than 16”, up to 19.2” (488mm) o/c, the standard is nominal ¾” (23/32”, 18.3 mm) T&G CD Exposure 1 Plywood suboor panels,
(Exposure 1) or nominal ¾ 23/32”, (18.3mm) OSB Exposure 1 suboor panels, 4’x8’ sheets, glued and mechanically fastened.
Truss/joist systems spaced over more than 19.2” (488mm) o/c up to a maximum of 24” (610mm) require minimum 7/8” T&G CD Exposure 1 Plywood
suboor panels, (Exposure 1), or minimum 7/8” OSB Exposure 1 suboor panels, 4x8’ sheets glued and mechanically fastened or two layers of
subooring or brace between the truss/joist in accordance with the truss/joist manufacturer’s recommendations and with local building codes. Some
truss/joist systems cannot be cross-braced and still maintain stability.
For existing wood oors install new ooring at right angles to the existing ooring.
Do not glue down hardwood ooring over particle board.
2
shawoors.com
For reference purposes only if printed or downloaded.