Data Sheet

Data sheet 3RK1105-1BG04-4CA0
ASIsafe extended Safety monitor 2 F-RO with integrated
safe slave 2 enabling circuits included Control of a safe
AS-i output Safe coupling IP20, with spring-type terminal
removable terminals Safe output relay Response time
max. 40 ms Monitor type 6, Version 3 Can be used up to
Category 4 (EN954-1) up to PL E (EN ISO 13849-1) up
to SIL 3 (IEC 61508)
General technical data:
Design of the product safety monitor, with expanded functionality
Protocol is supported AS-interface protocol Yes
Type 2 enabling circuits
Number of release circuits 2
Response time max. ms 40
Type of electrical connection of the inputs and
outputs
spring-loaded terminals
Rated operational current Ie
● AC-12, 50/60 Hz 250 V
A 3
● AC-15, 50/60 Hz
— 115 V
A 3
— 230 V
A 3
● DC-12 (DC-1) 24 V
A 3
● DC-13 (DC-11)
— 24 V
A 1
— 115 V
A 0.1
— 230 V
A 0.05
3RK1105-1BG04-4CA0 Subject to change without notice
Page 1/
3
09/13/2019 © Copyright Siemens