Datasheet

● for single-phase AC motor
— at 110/120 V rated value
0.25hp
— at 230 V rated value
0.5hp
● for three-phase AC motor
— at 200/208 V rated value
1hp
— at 220/230 V rated value
1.5hp
— at 460/480 V rated value
3hp
— at 575/600 V rated value
5hp
Contact rating of auxiliary contacts according to UL C300 / R300
Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current
Ik < 400 A)
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
gL/gG 50 A
● at 500 V
gL/gG 40 A
● at 690 V
gL/gG 40 A
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 90mm
Width 45mm
Depth 81mm
Connections/Terminals
Product function
● removable terminal for auxiliary and control
circuit
No
Type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control current circuit
screw-type terminals
Arrangement of electrical connectors for main current
circuit
Top and bottom
Type of connectable conductor cross-sections
● for main contacts
— single or multi-stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Type of connectable conductor cross-sections
3RV1011-1GA15 Subject to change without notice