Data Sheet
Height of the sensor 36mm
Length of the sensor 13mm
Width of the sensor 26mm
Material of the active sensor area Plastic, glass-fiber reinforced thermoplastic
Mechanical installation condition for sensor can be installed almost flush
Operating voltage rated value 30V
Operating current rated value 400mA
Operating power rated value 10W
Number of NC contacts for auxiliary contacts 2
Number of NO contacts for auxiliary contacts 1
Enclosure
Material of the enclosure Plastic, glass-fiber reinforced thermoplastic
Opening direction of the door right
Actuator
Design of the operating mechanism magnet
Contact
Switching frequency 5Hz
Safe operating distance OFF 15mm
Safe operating distance ON 5mm
Design of the switching function NC contact and NO contact
Number of switching contacts for signaling function 1
● safety-related
1
Connections/ Terminals
Type of electrical connection Latching connection 8 mm, 6-pole
Safety related data
B10 value
● with high demand rate acc. to SN 31920
12500000
Safety Integrity Level (SIL) acc. to IEC 61508 3
Proportion of dangerous failures
● with low demand rate acc. to SN 31920
50%
● with high demand rate acc. to SN 31920
50%
T1 value for proof test interval or service life acc. to
IEC 61508
20y
Inputs/ Outputs
Number of semiconductor outputs
● for signaling function
0
● safety-related
0
Number of outputs as contact-affected switching
element
● as NC contact
3SE6626-3CA01 Subject to change without notice
Page 2/
7
09/13/2019 © Copyright Siemens