Application

Application 2051 Point Database
13
Siemens Industry, Inc. Application Note, App 2051 140-1137
2014-05-01
Point
Number
Descriptor
Factory
Default
(SI Units)
2)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text Off Text
51 MTR 1 TIMING 130 SEC 1 0 -- --
{52} VLV 2 COMD 0 PCT 0.4 0 -- --
{53} VLV 2 POS 0 PCT 0.4 0 -- --
55 MTR 2 TIMING 130 SEC 1 0 -- --
56 MTR1 ROT ANG 90 -- 1 0 -- --
57 MTR2 ROT ANG 90 -- 1 0 -- --
58 MTR SETUP 0 -- 1 0 -- --
59 DO DIR. REV 0 -- 1 0 -- --
60 CYCLE FAN NO -- -- -- YES NO
63 CLG P GAIN 20.0 (36.0) -- 0.25 (0.45) 0 -- --
64 CLG I GAIN 0.01 (0.018) --
0.001
(0.0018)
0 -- --
65 CLG D GAIN 0 (0.0) -- 2 (3.6) 0 -- --
66 CLG BIAS 0 PCT 0.4 0 -- --
67 HTG P GAIN 10.0 (18.0) -- 0.25 (0.45) 0 -- --
68 HTG I GAIN 0.01 (0.018) --
0.001
(0.0018)
0 -- --
69 HTG D GAIN 0 (0.0) -- 2 (3.6) 0 -- --
70 HTG BIAS 0 PCT 0.4 0 -- --
{78} CTL TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0
(8.88888)
-- --
{79} CLG LOOPOUT 0 PCT 0.4 0 -- --
{80} HTG LOOPOUT 0 PCT 0.4 0 -- --
84 STAGE FAN 10 PCT 0.4 0 -- --
85 SWITCH LIMIT 5.2 PCT 0.4 0 -- --
86 SWITCH TIME 10 MIN 1 0 -- --
90 SWITCH DBAND 1.0 (0.56)
DEG F
(DEG C)
0.25 (0.14) 0 -- --
{92} CTL STPT
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0
(8.88888)
-- --
96 CAL TIMER 12 HRS 1 0 -- --
98 LOOP TIME 5 SEC 1 0 -- --
{99} ERROR STATUS 0 -- 1 0 -- --
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.