Data Sheet for Product

CP 567 Control Cabinets Technical Instructions
Document Number 155-272P25
October 12, 2017
Siemens Industry, Inc. Page 7
Cabinet Installation
(Flush Mount)
1. Mount the cabinet in a wall at least 6 inches (15.2 cm) deep. There are four
keyhole mounting holes in the back surface of the cabinet. Their sizes and
locations are shown in Figure 5. Use wall anchors that are suitable to support the
weight of the cabinet and its contents.
2. Determine the size of the knockouts required for the number and size of pneumatic
tubes and wires to be brought into the cabinet.
3. The cabinets are symmetrical before cutouts have been made, so the door can be
mounted with the hinge on the left or right side.
4. If more than one knockout is required, divide the tubes and wires for easy
connection to the controls.
5. If a cabinet light is required, order per instructions under Accessories. The
recommended mini work light has a 2-inch diameter by 4-inch long (51 mm ×
102 mm) bulb holder on a 15-inch (381 mm) long flexible metal arm.
a. Remove the plug and mounting bracket from the light.
b. Punch out the 7/16-inch (11 mm) diameter knockout in the center of the top of
the cabinet.
c. Attach the light using the nut and washer provided with it.
d. Wire the light cord in compliance with local electrical codes.
Figure 3. Flush Mount Cabinet Components.