Datasheet

Protection class
Protection class IP IP20, if the distribution board is installed, with connected
conductors
Energy limiting class 3
Switching capacity
Switching capacity current
● acc. to EN 60898 / rated value
10kA
● acc. to IEC 60947-2 / rated value
15kA
Rated residual switching capacity (IΔm) / according
to IEC 61009-1
10kA
Dissipation
Power loss [W] / for rated value of the current / at AC
/ in hot operating state / per pole
5.7W
Electricity
Tripping residual current / rated value 300mA
Tripping residual / rated value / derated current
● at 30 Cel
32A
● at 40 Cel
30.4A
● at 45 Cel
29.76A
● at 50 Cel
28.8A
● at 55 Cel
27.84A
● at 60 Cel
27.2A
● at 65 Cel
25.92A
● at 70 Cel
24.64A
Type of fault current A
Current / at AC / rated value 32A
Product details
Product feature / Touch protection Yes
Product feature
● halogen-free
Yes
● silicon-free
Yes
Product function
Product function / neutral conductor switching Yes
Number
Number of test cycles / for environmental testing /
acc. to IEC 60068-2-30
28
Connections
Connectable conductor cross-section / stranded
● minimum
0.75mm²
● maximum
35mm²
5SU1654-7KK32 Subject to change without notice
Page 2/
6
03/08/2019 © Copyright Siemens