Datasheet

● Outputs, adjustable
1kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules
Time of day
Clock
● Hardware clock (real-time)
Yes
● Backup time
480h; Typical
● Deviation per day, max.
±60 s/month at 25 °C
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological
functions
6; HSC (High Speed Counting)
Source/sink input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.
8
Input voltage
● Rated value (DC)
24V
● for signal "0"
5 V DC at 1 mA
● for signal "1"
15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
— at "0" to "1", min.
0.2ms
— at "0" to "1", max.
12.8ms
for interrupt inputs
— parameterizable
Yes
for technological functions
— parameterizable
Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80
kHz & 3 @ 30 kHz
Cable length
● shielded, max.
500m; 50 m for technological functions
● unshielded, max.
300m; for technological functions: No
Digital outputs
Number of digital outputs 6; Relays
Switching capacity of the outputs
● with resistive load, max.
2A
● on lamp load, max.
30 W with DC, 200 W with AC
Output delay with resistive load
● "0" to "1", max.
10ms; max.
6ES7212-1BE40-0XB0 Subject to change without notice
Page 3/
9
04/01/2020 © Copyright Siemens