Datasheet

● Limit class B, for use in residential areas
Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
CE mark Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max.
0.3m; five times, in product package
Ambient temperature during operation
● min.
-20°C
● max.
60°C; Number of simultaneously activated inputs or outputs 4 or
3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6
at 55 °C horizontal or 45 °C vertical
● horizontal installation, min.
-20°C
● horizontal installation, max.
60°C
● vertical installation, min.
-20°C
● vertical installation, max.
50°C
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Air pressure acc. to IEC 60068-2-13
● Operation, min.
795hPa
● Operation, max.
1080hPa
● Storage/transport, min.
660hPa
● Storage/transport, max.
1080hPa
Altitude during operation relating to sea level
● Installation altitude, min.
-1000m
● Installation altitude, max.
2000m
Relative humidity
● Operation, max.
95%; no condensation
Vibrations
● Vibration resistance during operation acc. to
IEC 60068-2-6
2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
● Operation, tested according to IEC 60068-2-6
Yes
Shock testing
6ES7212-1BE40-0XB0 Subject to change without notice
Page 8/