Data Sheet for Product

s Industry, Inc.
Building Technologies Division
3
FireFinder XLS Components (cont.’d)
Model ZIC-4A plugs into one (1) slot in the Model CC-5 or
Model CC-2 card cage, and has on-board LEDs for system
status and troubleshooting.
Indication of power, communication, internal operation,
and ground-fault conditions are provided, as well as
indication of circuit activation or Trouble conditions.
ZIC-8B / ZIC-2C Zone Indicating Cards
ZIC-8B / ZIC-2C
The Zone Indicating Card (Model ZIC-8B) provides eight (8)
fully supervised, programmable output circuits for use on
FireFinder XLS. Model ZIC-8B supplies eight (8) Class B
(Style Y) type output circuits, power limited to 2.0 amps
maximum per circuit. Each circuit can be independently
programmed for use with listed audible or visual notification
appliances, or listed emergency audio speakers. Model ZIC-
8B plugs into one (1) slot in the Model CC-5 or Model CC-2
card cage, and has on-board LEDs for system status.
Model ZIC-2C mounts directly on Model ZIC-8B, and
allows each of the Model ZIC-8B output circuits to be used
for two-channel voice applications. Indication of power,
communication, internal operation, and ground-fault
conditions are provided, as well as indication of circuit
activation or Trouble conditions.
DLC Device Loop Card
DLC Device Loop Card
The Device Loop Card (Model DLC) is the interface for
connection with FireFinder XLS detectors and initiating
devices including manual stations, control and input
devices. Model DLC plugs into one (1) slot of the CC-2 or CC-
5 card cage. Programming Model DLC is accomplished using
the FireFinder XLS system-programming tool, Zeus.
Model DLC takes one (1) address on the network, and
communicates with two (2) device circuits for a total of 252
detectors and devices. Model DLC has 12 LEDs for diagnostic
purposes, and provides ground-fault detection and zone-
isolation circuitry.
NI C-C Network Interface Card
NIC-C Network Interface Card
The Network Interface Card (Model NIC-C) provides HNET or
XNET network communications between enclosures. In
addition to the HNET or XNET communication, Model NIC-C
provides CAN network communication within an enclosure
or external to the enclosure. HNET or XNET communication
can be wired Style 4 or Style 7, but the CAN network can be
wired Style 4 only.
When used for HNET communications, Model NIC-C
provides contact between enclosures on a single system.
When Model NIC-C is used for XNET communications,
Model NIC-C provides communication between systems.
The maximum of XNET Model NIC-C cards on a single
system (single node) is one (1), for a total of 64 XNET
Model NIC-C cards on a peer-to-peer networked system.
Model NIC-C has diagnostic LEDs that indicate: Card Fail,
CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop A’ Fail
and Loop ‘B’ Fail. Model NIC-C Card also has LEDs to indicate
Power, Style and Active Networks.
HCP Control Point Module
HCP Control Point Module
Model HCP can be programmed as an independent,
remotely located telephone zone, speaker zone or
notification appliance circuit. Model HCP is designed to be
used with the Siemens Fire Safety Alarm Signaling
Devices product line.
Model HCP communicates through the Model DLC analog
loop, and can be wired either Class A’ (Style Z) or Class B’
(Style Y). The 24 VDC power input comes from either the
control panel or from any UL Listed power-limited,
auxiliary power supply.
MLC MXL Line Card [for FireFinder XLS]