Data Sheet for Product

s Industry, Inc.
Building Technologies Division
7
FireFinder XLS Components (cont.’d)
RNI Remote Network Interface
System-Status Display
SSD-Series System-Status Display
The System Status Display (SSD-series model displays) is a
remote LED / LCD display that shows the local status of a
FireFinder XLS system. An LED illuminates when Alarm,
Supervisory, Trouble, and Security events occur on the
system. A (4) four-line liquid-crystal display (LCD) will give
details of the event in alphanumeric form.
The display can be toggled to display additional events.
Optional remote system control capabilities are available.
Models SSD-C, SSD-C-INT, and Model SSD-C-REM have
three (3) additional control buttons to Acknowledge
events; silence audible circuits, and reset the system.
Models SSD-C and SSD-C-INT have an integral keyswitch
that enables these control buttons to operate. Model SSD-
C-REM is located within a locked cabinet. Therefore, no
additional keyswitch is required for manual activation of
the control buttons.
IIC Interface Isolation Card
IIC Interface Isolation Card
The Interface Isolation Card (Model IIC) is designed to
isolate network signals when used with a Model NCC ring
configuration, via Model NRC. Model IIC executes the
aforementioned isolation by removing the backplane
network signals from each Model CC-2 card cage. Model
IIC also provides one (1) end of CAN termination on each
side of Model CC-2.
XDACT-ASSY XDACT Assembly
XDACT-ASSY XDACT Assembly
The XDACT Assembly (Model XDACT-ASSY) is the blank plate
used for holding the optional Digital Alarm Communication
Transmitter (DACT), Model FCA2015-U1 on FireFinder XLS.
Model XDACT-ASSY can be mounted on all CAB-series
enclosures. Each assembly must be located in the Global
Person Machine Interface cabinet for global configurations.
Available communication protocols on a DACT module
include: SIA DCS 8 | SIA DCS 20 | Ademco Contact ID.
CAB1 Single Row Enclosure
CAB1 Single Row Enclosure
Model CAB 1, the smallest of the FireFinder XLS
enclosures, can house a single Model CAB-MP cabinet
mounting plate for mounting card cages, power supplies
and bulk amplifiers. Model CAB1 also has four (4)
mounting slots on the inner door for mounting The Person
Machine Interface and Model ID-MP switch module
brackets.
Model CAB1 comes complete with a black back box; black
inner and outer doors; a single lock and key set on the outer
door; a single, installed cabinet mounting plate (Model
CAB-MP), and a single, installed outer door lens plate
(Model OD-LP). A red version (Model CAB1-R) is also
available.
Approximate size: 27 (68.6cm.) high, 26 (66cm.)
wide, and 8 (20.3cm.) deep.