Data Sheet for Product

Table Of Contents
7/14
Siemens 2-port and 3-port Terminal Unit Valves PN16 CA1N4847en
Smart Infrastructure 2021-07-16
Commissioning
Commission the valve only if the manual knob or actuator have been mounted
correctly.
The straight-through control path A AB can be opened either electrically via the
actuator, or by adjustment with the manual button. In the case of 3-port valves, this
throttles or closes bypass B.
Maintenance
V..P47..(S) valves require no maintenance.
When doing service work on the valve / actuator:
Deactivate the pump and turn off the power supply
Close the shutoff valves
Fully reduce the pressure in the piping system and allow pipes to completely cool
down
If necessary, disconnect the electrical wires.
Before putting the valve into operation again, make certain the manual knob or the
actuator is correctly fitted.
The stem sealing gland cannot be exchanged. In the case of leakage, the entire valve
must be replaced. Contact your local office or branch.
Disposal
Do not dispose of the device as household waste.
Warning
Due to the tensioned spring return, valve disassembly may result in flying parts causing
possible injury.
Only authorized staff may disassemble valves with tensioned spring return!
Disposal
Special handling of individual components may be mandated by law or make
ecological sense.
Observe all local and currently applicable laws and regulations.
Warranty
The technical data supplied for these valves is valid only for valves used in
conjunction with the actuators listed under "Equipment combinations", page 3.
Use with third-party actuators invalidates any warranty offered by Siemens
Switzerland Ltd / HVAC Products.
Manual adjustment
Warning
Stem sealing gland