Revision A Siemens BT300 HVAC Drive Application Manual www.sbt.siemens.
Siemens Industry, Inc. • 1 table of contents Document ID:DPD01149B Rev. B Revision release date: February 12, 2013 1. Siemens BT300 - Startup..................................................................................3 1.1 1.2 1.3 Startup Wizard ............................................................................................................................. 3 PID Mini-Wizard ...............................................................................................................
Siemens Industry, Inc. • 2 3.7.1 Fault appears............................................................................................................................. 95 3.7.2 Fault history ............................................................................................................................... 95 3.7.3 Fault codes ................................................................................................................................
Siemens BT300 - Startup Siemens Industry, Inc. • 3 1. SIEMENS BT300 - STARTUP 1.1 Startup Wizard In the Startup Wizard, you will be prompted for essential information needed by the drive so that it can start controlling your process. In the Wizard, you will need the following keypad buttons: Left/Right arrows. Use these to easily move between digits and decimals. Up/Down arrows. Use these to move between options in menu and to change value. OK button. Confirm selection with this button.
Siemens Industry, Inc. • 4 9 10 11 Siemens BT300 - Startup Set value for Motor nominal current (according to nameplate) Set value for Minimum frequency Range: Varies Range: 0.00...60.00 Hz Set value for Maximum frequency Range: 0.00...320.00 Hz Now the Startup Wizard is done. The Startup Wizard can be re-initiated by activating the parameter Restore factory defaults (par. P6.5.1) in the Parameter backup sub-menu (M6.5) OR with parameter P1.19 in the Quick setup menu. 1.
Siemens BT300 - Startup 11 Sleep function? Siemens Industry, Inc. • 5 No Yes If option ‘Yes’ is selected you will be prompted for three more values: 12 13 14 1.3 Sleep frequency limit 1 0.00...320.00 Hz Sleep delay 1 0...3000 s Wake-up level 1 Range depends on selected process unit. Multi-pump mini-wizard The Multi-Pump mini-wizard asks the most important questions for setting up a Multi-Pump system. The PID mini-wizard always precedes the Multi-Pump mini-wizard.
Siemens Industry, Inc.
Keypad of the drive 2. Siemens Industry, Inc. • 7 KEYPAD OF THE DRIVE The control keypad with graphical interface is the interface between the Siemens BT300 variable frequency drive and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the variable frequency driver's parameters.
Siemens Industry, Inc. • 8 2.1 Keypad of the drive Siemens keypad with graphical display The graphical keypad features an LCD display and 9 buttons. 2.1.1 Keypad display The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about his present location in the menu structure and the item displayed. See the attached Keypad Navigation Map to get a comprehensive idea of the menu structure. 2.1.1.
Keypad of the drive READY I/O STOP ID:172 READY Start/Stop Setup M3.2.1 I/O ID: Edit KeypadStopButton Yes Help Start Function Ramping Add to favorites I/O Ctrl. Place Auto M3.2.1 FieldbusCTRL STOP OR: READY M3.2.1 Ctrl. Place Auto I/O Control STOP Ctrl. Place Auto READY I/O Start/Stop Setup ID:172 M3.2.1 I/O Control STOP Ctrl. Place Auto I/O Control KeypadStopButton Yes READY BACK RESET I/O Ctrl. Place Auto M3.2.
Siemens Industry, Inc. • 10 STOP READY Keypad of the drive Keypad STOP Ready Main Menu ID: M1 Monitor ( 12 ) Parameters ( 21 ) Diagnostics ( 6 ) STOP STOP READY ? ID: ID:1805 Hand Auto READY Keypad Choose action Keypad Hand/Auto ID: ID:211 Change direction Control page Hand Hand/Auto Auto I/O Main Menu M1 Parameters ( 21 ) Diagnostics ( 6 ) BT11114 ID: Monitor ( 12 ) Figure 4. Changing control places.
Keypad of the drive Siemens Industry, Inc. • 11 Before any parameters can successfully be copied from one drive to another, the drive has to be stopped when the parameters are downloaded. • • • First go into User settings menu and locate the Parameter backup sub-menu. In the Parameter backup sub-menu, there are three possible functions to be selected: Restore factory defaults will re-establish the parameter settings originally made at the factory.
Siemens Industry, Inc. • 12 2.1.2.6 Keypad of the drive Adding an item to Favorites You might need to refer to certain parameter values or other items often. Instead of locating them one by one in the menu structure, you may want to add them to a folder called Favorites, where they can easily be reached. To remove an item from the Favorites, see Chapter 2.2.7. READY I/O STOP READY I/O STOP Motor Nom Freq Basic Settings Motor Nom Voltg 230.00 V Edit Motor Nom Freq 50.
Keypad of the drive Siemens Industry, Inc. • 13 2.2 Menu structure 2.2.1 Quick setup The Quick Setup Menu includes the minimum set of most commonly used parameters during installation and commissioning. You can find more detailed information on the parameters of this group in Chapter 3.3. 2.2.2 Monitor Multi-monitor On the multi-monitor page, you can collect nine values that you wish to monitor.
Siemens Industry, Inc. • 14 2.2.3 Keypad of the drive Parameters Through this sub-menu, you can reach the application parameter groups and parameters. You can find more information on parameters in Chapter 3. 2.2.4 Diagnostics Under this menu, you can find Active faults, Reset faults, Fault history, Counters and Software info. 2.2.4.1 Active faults Menu Function Note Active faults When a fault/faults display(s), the display with the name of the fault starts to blink.
Keypad of the drive 2.2.4.4 Siemens Industry, Inc. • 15 Total counters Table 1: Diagnostics menu, Total counters parameters. Code Parameter Min Max Unit Default ID Description V4.4.1 Energy counter Varies Amount of energy taken 2291 from supply network. No reset. V4.4.3 Operating time y d hh:mm 2298 Control unit operating time V4.4.7 Run time y d hh:mm 2293 Motor running time V4.4.11 Power on time y d hh:mm Amount of time the power 2294 unit has been powered so far. No reset. V4.
Siemens Industry, Inc. • 16 2.2.5 Keypad of the drive I/O and hardware Various options-related settings are located in this menu. 2.2.5.1 Basic I/O Monitor here the status of inputs and outputs. Table 4: I/O and Hardware menu, Basic I/O parameters. Code Parameter Min Max V5.1.1 Digital input 1 0 1 Status of digital input signal V5.1.2 Digital input 2 0 1 Status of digital input signal V5.1.3 Digital input 3 0 1 Status of digital input signal V5.1.
Keypad of the drive 2.2.5.2 Siemens Industry, Inc. • 17 Option board slots The parameters of this group depend on the option board installed. If no option board is placed in slots D or E, no parameters are visible. See Chapter 3.5.1 for the location of the slots. When an option board is removed, info text “F39 Device removed” will display. See Table 3.7.3. Menu Function Note Slot D Settings Option board related settings. Monitoring Monitor option board-related info.
Siemens Industry, Inc. • 18 2.2.5.5 Keypad of the drive Keypad Table 7: I/O and Hardware menu, Keypad parameters. Code P5.6.1 Parameter Timeout time P5.6.2 Default page P5.6.3 Menu index P5.6.4 Contrast P5.6.5 2.2.5.6 Min Backlight time Max 0 60 0 Unit mm 4 Default ID Description 0 Time after which the display returns to page defined with parameter P5.6.2.
Keypad of the drive 2.2.6 Siemens Industry, Inc. • 19 User settings Table 8: User settings menu, General settings. Code Parameter Min Max P6.1 Language selections Varies Varies P6.2 Application selection M6.5 Parameter backup P6.7 Drive name 2.2.6.1 Unit Default ID Varies 802 Description Depends on language package. 801 See Chapter 2.2.6.1 below. Give name of drive if needed. Parameter backup Table 9: User settings menu, Parameter backup parameters.
Siemens Industry, Inc. • 20 2.2.7 Keypad of the drive Favorites Favorites are typically used to collect a set of parameters or monitoring signals from any of the keypad menus. You can add items or parameters to the Favorites folder, see Chapter 2.1.2.6. To remove an item or a parameter from the Favorites folder, do the following: STOP READY I/O STOP READY Favorites I/O Motor Nom Freq Monitor Motor Nom Freq 50.00 Hz BT9172 Help Rem from favorites 2.2.
Siemens Application 3. Siemens Industry, Inc. • 21 SIEMENS APPLICATION The Siemens drive contains a preloaded application for instant use. The parameters of this application are listed in Chapter 3.5 of this manual and explained in more detail in Chapter 3.6. 3.
Siemens Industry, Inc. • 22 3.2 Siemens Application Example of control connections Table 11. Connection example, standard I/O board. Standard I/O board Terminal Reference potentiometer 1...10 kW Remote reference 4...20mA/0...10V (programmable) Signal 1 +10 Vref Reference output 2 AI1+ Analog input, voltage or current* 3 AI1- Analog input common (current) 4 AI2+ Analog input, voltage or current 5 AI2- Analog input common (current) 6 24Vout 24V aux.
Siemens Application Siemens Industry, Inc. • 23 Table 12. Connection example, Relay board 1. From Standard I/O board From term. #6 or 12 Relay board 1 Default From term. #13 Terminal RUN 21 RO1/1 NC 22 RO1/2 CM 23 RO1/3 NO 24 RO2/1 NC 25 RO2/2 CM 26 RO2/3 NO 32 RO3/1 CM 33 RO3/2 NO Signal Relay output 1 RUN Relay output 2 FAULT Relay output 3 READY Table 13. Connection example, Relay board 2. From Standard I/O board From term. #12 Relay board 2 From term. #13 RUN 3.
Siemens Industry, Inc. • 24 Siemens Application Table 14: Quick setup parameter group. Code Parameter Min Max Unit Default ID Description P1.6 Motor nominal power Varies Varies kW Varies 116 Find this value In on the rating plate of the motor. P1.7 Motor current limit Varies Varies A Varies 107 Maximum motor current from drive. P1.8 Minimum frequency 0.00 P3.3.1 Hz Varies 101 Minimum allowed frequency reference. P1.9 Maximum frequency P3.3.1 320.00 Hz 60.
Siemens Application 3.4.2 Siemens Industry, Inc. • 25 Basic See Table 14 in which the basic monitoring values are presented. NOTE: Only Standard I/O board status are available in the Monitor menu. Status for all I/O board signals can be found as raw data in the I/O and Hardware system menu. Check expander I/O board status when required in the I/O and Hardware system menu. Table 15: Monitoring menu items. Code V2.2.
Siemens Industry, Inc. • 26 Siemens Application Table 15: Monitoring menu items. Code V2.2.22 Monitoring value Unit Motor current with 1 decimal ID Description 45 Motor current monitor value with a fixed number of decimals and less filtering. Can be used e.g. for fieldbus purposes to always get the right value regardless of frame size, or monitoring when less filtering time is needed for the motor current. V2.2.23 Appl.StatusWord 1 89 Bit coded Application Status Word 1.
Siemens Application 3.4.4 Siemens Industry, Inc. • 27 PID1 controller monitoring Table 17: PID1-controller value monitoring. Code Unit ID PID1 setpoint Varies 20 Process units selected with parameter V2.4.2 PID1 feedback Varies 21 Process units selected with parameter V2.4.3 PID1 error value Varies 22 Process units selected with parameter V2.4.
Siemens Industry, Inc. • 28 3.4.7 Siemens Application Fieldbus data monitoring Table 20: Fieldbus data monitoring Code V2.8.1 Monitoring value FB Control Word Unit ID Description 874 Fieldbus control word used by application in bypass mode/ format. Depending on the fieldbus type or profile the data can be modified before sent to application. V2.8.2 FB speed reference 875 Speed reference scaled between minimum and maximum frequency at the moment it was received by the application.
Siemens Application 3.4.8 Siemens Industry, Inc. • 29 Temperature inputs monitoring Table 21: Temperature inputs monitoring Code P2.9.1 P2.9.2 P2.9.3 Parameter Temp.Input 1 Temp.Input 2 Temp.Input 3 Min -50.0 -58.0 -50.0 -58.0 -50.0 -58.0 24-hour support +1-800-877-7545 (Dial 2) Max 200.0 398.0 200.0 398.0 200.0 398.0 Unit °C °F °C °F °C °F Default 200.0 398.0 200.0 398.0 200.0 398.0 ID Description 50 Measured value of Temperature Input 1.
Siemens Industry, Inc. • 30 3.5 Siemens Application Application parameter lists Find the parameter menu and the parameter groups as guided below. READY Keypad ID: M3 Quick Setup ( 17 ) Monitor ( 6 ) Parameters ( 13 ) STOP Main Menu READY Keypad Parameters ID: M3.1 Motor Settings ( 2 ) Start/Stop Setup ( 7 ) BT11091 STOP References ( 18 ) The application contains the following parameter groups: Table 22. Parameter groups. Menu and Parameter group Group 3.
Siemens Application 3.5.1 Siemens Industry, Inc. • 31 Parameter programming The programming of digital inputs in the Siemens application is very flexible. There are no digital terminals assigned only for certain function. You can choose the terminal of your choice for the certain function, in other words, functions appear as parameters which the operator defines a certain input for. For a list of functions for the digital inputs, see Table32 on page 45.
Siemens Industry, Inc. • 32 Siemens Application EXAMPLE: You want to connect the Control signal 2 A (parameter P3.5.1.2) to digital input DI2 on Standard I/O board. 3.5.1.1 Example programming with graphical keypad 1 Locate the parameter Control signal 2 A (P3.5.1.2) on the keypad. STOP READY Keypad STOP Main Menu ID: M3 Quick Setup ( 17 ) Monitor ( 5 ) Parameters ( 12 ) STOP READY READY Keypad ID: STOP READY Parameters M3.
Siemens Application 3.5.1.2 3.5.2 Siemens Industry, Inc. • 33 Descriptions of signal sources: Table 23. Descriptions of signal sources. Source Function Slot0 1 = Always FALSE, 2-9 = Always TRUE SlotA Number corresponds to digital input in the slot. SlotB Number corresponds to digital input in the slot. SlotC Number corresponds to digital input in the slot. SlotD Number corresponds to digital input in the slot. SlotE Number corresponds to digital input in the slot.
Siemens Industry, Inc. • 34 Siemens Application 3.5.3 Group 3.1: Motor settings 3.5.3.1 Basic Settings Table 24: Basic motor settings. Code Parameter Min Max Unit Default ID Description Varies Varies V Varies 110 Find this value Un (V) on the rating plate of the motor. This parameter sets the voltage at the field weakening point to 100% * Un (V) Motor. Note also used connection (Delta/Star). 8.00 320.00 Hz Varies 111 Find this value fn on the rating plate of the motor.
Siemens Application Siemens Industry, Inc. • 35 Table 25: Advanced motor settings. Code Parameter P3.1.2.5 Motor preheat function P3.1.2.6 Motor preheat temperature limit P3.1.2.7 Motor preheat current Min 0 -20 0 Max Unit 3 80 0.
Siemens Industry, Inc. • 36 Siemens Application Auto control place (I/O B): Start, stop and reverse commands are controlled by 2 digital inputs chosen with parameters P3.5.1.3 and P3.5.1.4. The functionality/logic for these inputs is then selected with parameter P3.2.7 (in this group). Hand control place (Keypad): Start and stop commands come from the keypad buttons, while the direction of rotation is selected by the parameter P3.3.7.
Siemens Application 3.5.5 Siemens Industry, Inc. • 37 Group 3.3: Control reference settings The frequency reference source is programmable for all control places except PC, which always takes the reference from the PC tool. Auto control place (I/O A): The source of frequency reference can be selected with parameter P3.3.3. Auto control place (I/O B): The source of frequency reference can be selected with parameter P3.3.4. Hand control place (Keypad): If the default selection for parameter P3.3.
Siemens Industry, Inc. • 38 Siemens Application Table 27: Control reference settings. Code P3.3.9 Parameter Fieldbus control reference selection P3.3.10 Preset frequency mode Min 1 Max Unit 8 Default ID Description 122 Selection of ref source when control place is Fieldbus: 1 = Preset frequency 0 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = AI1+AI2 7 = PID 1 reference 8 = Motor potentiometer 0 182 0 = Binary coded 1 = Number of inputs.
Siemens Application 3.5.6 Siemens Industry, Inc. • 39 Group 3.4: Ramp & Brakes Setup Two ramps are available (two sets of acceleration time, deceleration time and ramp shape). The second ramp can be activated by a digital input. NOTE: Ramp 2 always has higher priority and is used if a digital input for ramp selection is activated or the Ramp 2 threshold is smaller than RampFreqOut. Table 28: Ramp and brakes setup. Code P3.4.1 P3.4.
Siemens Industry, Inc. • 40 Siemens Application 3.5.7 Group 3.5: I/O Configuration 3.5.7.1 Digital inputs Digital inputs are very flexible to use. Parameters are functions that are connected to the required digital input terminal. The digital inputs are represented as, for example, DigIN Slot A.2, meaning the second input on slot A. It is also possible to connect the digital inputs to time channels which are also represented as terminals.
Siemens Application Siemens Industry, Inc. • 41 Table 29: Digital input settings. Code Parameter Default ID Description P3.5.1.24 PID2 select setpoint DigIN Slot0.1 1048 FALSE = Setpoint 1 TRUE = Setpoint 2 P3.5.1.25 Motor 1 interlock DigIN Slot0.1 426 FALSE = Not active TRUE = Active P3.5.1.26 Motor 2 interlock DigIN Slot0.1 427 FALSE = Not active TRUE = Active P3.5.1.27 Motor 3 interlock DigIN Slot0.1 428 FALSE = Not active TRUE = Active P3.5.1.
Siemens Industry, Inc. • 42 3.5.7.2 Siemens Application Analog inputs Table 30: Analog input settings. Code Parameter P3.5.2.1 AI1 signal selection P3.5.2.2 AI1 signal filter time P3.5.2.3 Min Max Unit s Default ID Description AnIN SlotA.1 377 Connect the AI1 signal to the analog input of your choice with this parameter. Programmable 1.0 378 Filter time for analog input 0 379 0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA 0.00 300.00 AI1 signal range 0 1 P3.5.2.4 AI1 custom.
Siemens Application Siemens Industry, Inc. • 43 Table 30: Analog input settings. Code Parameter P3.5.2.29 AI5 custom. max P3.5.2.30 AI5 signal inversion P3.5.2.31 AI6 signal selection P3.5.2.32 AI6 signal filter time P3.5.2.33 Min Max Unit Default ID -160.00 160.00 % 100.00 192 Custom range max setting 0 1 0 198 0 = Normal 1 = Signal inverted AnIN Slot0.1 199 See P3.5.2.13. Programmable 1.0 200 See P3.5.2.14. 0 201 0 = 0…10 V / 0…20 mA 1 = 2…10 V / 4…20 mA 0.00 300.
Siemens Industry, Inc. • 44 3.5.7.3 Siemens Application Digital outputs, slot B (Basic) Table 31: Digital output settings on standard I/O board. Code Parameter P3.5.3.2.1 Basic R01 function P3.5.3.2.
Siemens Application 3.5.7.4 Siemens Industry, Inc. • 45 Expander slots D and E digital outputs Table 32: Slot D/E digital outputs. Code Parameter Min Max Unit Default ID Shows only parameters for existing outputs in slot D/E. Selections as in Basic R01 Not visible if no digital output exists in slot D/E. Application dynamic output list 3.5.7.5 Description Analog outputs, Slot A (Standard) Table 33: Standard I/O board analog output settings. Code Parameter Min Max P3.5.4.1.
Siemens Industry, Inc. • 46 3.5.7.6 Siemens Application Expander slots D to E analog outputs Table 34: Slot D/E analog outputs. Code Parameter Min Max Unit Default ID Shows only parameters for existing outputs in slot D/E. Selections as in Basic AO1 Not visible if no analog output exists in slot D/E. Application dynamic output list 3.5.8 Description Group 3.6: Fieldbus Data Mapping Table 35: Fieldbus data mapping. Code Parameter Min Max Unit Default ID Description P3.6.
Siemens Application 3.5.9 Siemens Industry, Inc. • 47 Group 3.7: Prohibited Frequencies In some systems it may be necessary to avoid certain frequencies due to mechanical resonance problems. By setting up prohibit frequencies, it is possible to skip these ranges. Table 37: Prohibited Frequencies. Code Parameter Min Max Unit Default ID Description P3.7.1 Prohibited frequency range 1 low limit -1,00 320,00 Hz 0,00 509 0 = Not used P3.7.
Siemens Industry, Inc. • 48 3.5.10 Siemens Application Group 3.8: Limit supervisions Choose here: 1. 2. 3. 4. One or two (P3.8.1/P3.8.5) signal values for supervision. Whether the low or high limits are supervised (P3.8.2/P3.8.6) The actual limit values (P3.8.3/P3.8.7). The hysteresis for the set limit values (P3.8.4/P3.8.8). Table 38: Limits supervision settings. Code P3.8.1 Parameter Supervision #1 item selection P3.8.2 Supervision #1 mode P3.8.
Siemens Application 3.5.11 Siemens Industry, Inc. • 49 Group 3.9: Protections Parameters of Motor thermal protection (P3.9.6 to P3.9.10) The motor thermal protection is to protect the motor from overheating. The drive is capable of supplying higher than nominal current to the motor. If the load requires this high current, there is a risk that the motor will thermally overload. This is the case especially at low frequencies.
Siemens Industry, Inc. • 50 Siemens Application Table 39: Protections settings. Code Parameter Min Max Unit Default ID Description P3.9.2 Response to external fault 0 3 2 701 0 = No action 1 = Alarm 2 = Fault (Stop according to stop mode) 3 = Fault (Stop by coasting) P3.9.3 Response to Input phase fault 0 3 3 730 See above P3.9.4 Undervoltage fault 0 1 0 727 0 = Fault stored in history 1 = Fault not stored in history P3.9.
Siemens Application Siemens Industry, Inc. • 51 Table 39: Protections settings. Code Parameter Min Max P3.9.19 Response to Fieldbus communication fault 0 P3.9.20 Slot communication fault 0 Unit Default ID Description 4 3 733 See P3.9.1 3 2 734 See P3.9.2 See P3.9.2 P3.9.21 Thermistor fault 0 3 0 732 It is recommended to set this value to 2 if an option card is installed which has a thermistor present. P3.9.22 Response to PID1 supervision fault 0 3 2 749 See P3.9.2 P3.9.
Siemens Industry, Inc. • 52 3.5.12 Siemens Application Group 3.10: Automatic reset Table 40: Autoreset Settings. Code P3.10.1 Parameter Automatic reset P3.10.2 Restart function P3.10.3 Wait time P3.10.4 Trial time P3.10.5 Min Max 0 1 0 1 0,10 10000,0 Unit s s Default ID Description 0 731 0 = Disabled 1 = Enabled 1 719 The start mode for Automatic reset is selected with this parameter: 0 = Flying start 1 = According to par. P3.2.
Siemens Application 3.5.13 Siemens Industry, Inc. • 53 Group 3.11: Timer functions The time functions (Time Channels) in the Siemens BT300 give you the possibility to program functions to be controlled by the internal RTC (Real Time Clock). Practically every function that can be controlled by a digital input can also be controlled by a Time Channel. Instead of having an external PLC controlling a digital input you can program the "closed" and "opened" intervals of the input internally.
Siemens Industry, Inc. • 54 Siemens Application Timers Timers can be used to set a Time Channel active during a certain time by command from a digital input (or a Time Channel). Remaining time Time Activation Duration OUT 9137.emf Figure 12. Activation signal comes from a digital input or "a virtual digital input" such as a Time channel. The Timer counts down from falling edge.
Siemens Application Siemens Industry, Inc. • 55 Timer 1 The manual bypassing can be handled by a digital input 1 on slot A (by a different switch or connection to lighting). P3.11.6.1: Duration: 1800s (30min) P3.11.6.2: Assign to channel: Time channel 1 P3.5.1.18: Timer 1: DigIn SlotA.1 (Parameter located in digital inputs menu.
Siemens Industry, Inc. • 56 Siemens Application Table 41: Timer functions. Code Parameter Min Max Unit 00:00:00 23:59:59 hh:mm:ss Default ID Description P3.11.3.2 OFF time P3.11.3.3 From day P3.11.3.4 To day 0 6 0 1477 See Interval 1 P3.11.3.5 Assign to channel 0 3 0 1478 See Interval 1 1479 See Interval 1 0 6 00:00:00 1475 See Interval 1 0 1476 See Interval 1 3.11.4 INTERVAL 4 P3.11.4.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 P3.11.4.
Siemens Application Siemens Industry, Inc. • 57 3.5.14 Group 3.12: PID-controller 1 3.5.14.1 Basic settings Table 42: PID Basic Settings. Code P3.12.1.1 P3.12.1.2 Parameter PID gain PID integration time P3.12.1.3 PID derivation time P3.12.1.4 Process unit selection Min 0.00 0.00 Max 1000.00 600.00 0.00 100.00 1 38 Unit % s s Default 100.00 1.00 0.
Siemens Industry, Inc. • 58 Siemens Application Table 42: PID Basic Settings. Code P3.12.1.9 P3.12.1.10 Parameter Dead band hysteresis Dead band delay Min Varies 0.00 Max Varies 320.00 Unit Varies s Default ID Description 0 Dead band area around the setpoint in process units.The PID output is locked if the 1056 feedback stays within the dead band area for a predefined time. 0.00 If the feedback stays within the dead band area for a pre1057 defined time, the output is locked.
Siemens Application 3.5.14.2 Siemens Industry, Inc. • 59 Setpoints Table 43: PID Setpoints. Code Parameter Min Max Unit Default ID P3.12.2.1 Keypad setpoint 1 Varies Varies Varies 0 167 P3.12.2.2 Keypad setpoint 2 Varies Varies Varies 0 168 P3.12.2.3 Setpoint ramp time P3.12.2.4 Setpoint source 1 selection P3.12.2.5 P3.12.2.6 P3.12.2.7 P3.12.2.8 0.00 300.0 0 16 Setpoint 1 minimum -200.00 200.00 Setpoint 1 maximum -200.00 200.
Siemens Industry, Inc. • 60 Siemens Application Table 43: PID Setpoints. Code Parameter Min Max Unit Default ID Description P3.12.2.12 Setpoint 2 minimum -200.00 200.00 % 0.00 1073 Minimum value at analog signal minimum. P3.12.2.13 Setpoint 2 maximum -200.00 200.00 % 100.00 1074 Maximum value at analog signal maximum. P3.12.2.14 Sleep frequency limit 2 0.00 320.00 Hz 0.00 P3.12.2.15 Sleep delay 2 0 3000 P3.12.2.16 Wake-up level 2 P3.12.2.17 Setpoint 2 boost 3.5.14.
Siemens Application Siemens Industry, Inc. • 61 Table 44: PID Feedback. Code Parameter Min Max 0 14 Unit Default ID Description 0 335 See P3.12.3.3 P3.12.3.6 Feedback 2 source selection P3.12.3.7 Feedback 2 minimum -200.00 200.00 % 0.00 338 Minimum value at analog signal minimum. P3.12.3.8 Feedback 2 maximum -200.00 200.00 % 100.00 339 Maximum value at analog signal maximum.
Siemens Industry, Inc. • 62 3.5.14.4 Siemens Application Feedforward Feedforward usually needs accurate process models, but in some simple cases a gain + offset type of feedforward is enough. The feedforward part does not use any feedback measurements of the actual controlled process value (water level in the example on page 87). Siemens feedforward control uses other measurements which are indirectly affecting the controlled process value. Table 45: Feedforward. Code Parameter Min Max P3.12.4.
Siemens Application 3.5.14.6 Siemens Industry, Inc. • 63 Pressure Loss Compensation Table 47: Pressure Loss Compensation. Code Parameter P3.12.6.1 Enable setpoint 1 P3.12.6.2 Setpoint 1 max compensation P3.12.6.3 Enable setpoint 2 P3.12.6.4 Setpoint 2 max compensation Min 0 Max 1 Varies Varies 0 1 Varies Varies 24-hour support +1-800-877-7545 (Dial 2) Unit Varies Varies Default ID Description 0 Enables pressure loss compensation for setpoint 1.
Siemens Industry, Inc. • 64 Siemens Application 3.5.15 Group 3.13: PID-controller 2 3.5.15.1 Basic settings For more detailed information, see Chapter 3.5.14. Table 48: PID-2 Basic Settings. Code P3.13.1.1 P3.13.1.2 Parameter Enable PID Output in Stop Min Max 0 1 0.0 100.0 Unit % Default ID 0 1630 0.
Siemens Application Siemens Industry, Inc. • 65 Table 48: PID-2 Basic Settings. Code Parameter Min Max Unit Default ID Description The setpoint and feedback values are internally handled as percent, but can be P3.13.1.7 Process unit min Varies Varies Varies 0 scaled to process units on the panel. Process Unit selection 1664 selects unit. Process Unit Min and Max are the process values corresponding to 0% and 100% respectively (scaled linearly in between).
Siemens Industry, Inc. • 66 Siemens Application Table 48: PID-2 Basic Settings. Code Parameter Min Max Unit Default ID Description Dead band around the setpoint. When we are within this area the PID P3.13.1.12 3.5.15.2 Dead band delay 0.00 320.00 s 0.00 controller output will be locked. The size of the Dead 1638 Band area around the setpoint is set in process units. I.e. 2 bar will give us a dead band of +- 2bar around the setpoint.
Siemens Application 3.5.15.3 Siemens Industry, Inc. • 67 Feedback For more detailed information, see Chapter 3.5.14. Table 50: PID-2 Feedback Code Parameter Min P3.13.3.1 Feedback function Feedback function P3.13.3.2 gain P3.13.3.3 1 -1000.0 Feedback 1 source selection Max Unit 9 1000.0 Default 1 % 100.0 Description Choose a single signal used as feedback or make calcula1650 tions based on one or two signals.
Siemens Industry, Inc. • 68 Siemens Application Table 51: PID-2 Process Supervision. Code Parameter Min Max Unit Default ID Description Process supervision is used to supervise that the actual value stays within P3.13.4.3 Lower limit Varies Varies Varies Varies some predefined limits. With this function we can e.g. 1661 detect a major pipe burst and stop unnecessary flooding. An upper and lower limit for the supervision range can be set, including a delay when trigging faults. P3.13.4.
Siemens Application 3.5.16 Siemens Industry, Inc. • 69 Group 3.14: Multi-pump The Multi-pump functionality allows you to control up to 4 motors (pumps, fans) with PID controller 1. The drive is connected to one motor which is the "regulating" motor connecting and disconnecting the other motors to/from the mains by means of contactors controlled with relays when needed in order to maintain the right setpoint.
Siemens Industry, Inc. • 70 3.5.17 Siemens Application Group 3.16: Fire mode The drive ignores all commands from the keypad, fieldbuses and the PC tool and runs at preset frequency when activated. If activated, the alarm sign is shown on the keypad and the warranty is void. In order to enable the function, you need to set a password in the description field for parameter Fire Mode password.
Siemens Application 3.6 Siemens Industry, Inc. • 71 HVAC Application - Additional parameter information Due to its simplicity of use, most parameters of the Siemens Application only require a basic description, which is given in the parameter tables in Chapter 3.5. In this chapter, you will find additional information on some of the more advanced application parameters. Should you not find the information you need, please contact Technical Support. Motor current limit (P3.1.1.
Siemens Industry, Inc. • 72 Siemens Application Stop function (P3.2.5) Selection number Selection name Description 0 Coasting The motor is allowed to stop on its own inertia. The control by the drive is discontinued and the drive current drops to zero as soon as the stop command is given. 1 Ramp After the Stop command, the speed of the motor is decelerated according to the set deceleration parameters to zero speed. I/O A start/stop logic (P3.2.6) Values 0...
Siemens Application Selection number Siemens Industry, Inc. • 73 Selection name CS1: Forward CS2: Backward 0 FWD Note The functions take place when the contacts are closed. Output frequency Set frequency t 0 Hz Set frequency REV Run enable Ctrl signal 1 Ctrl signal 2 Keypad start button Keypad stop button 1 2 3 4 5 6 7 8 9 10 11 12 13 9135.emf Figure 15. I/O A Start/Stop logic = 0. Explanations: 1 Control signal (CS) 1 activates causing the output frequency to rise.
Siemens Industry, Inc. • 74 Selection number Siemens Application Selection name Note CS1: Forward (edge) CS2: Inverted stop 1 FWD Output frequency Set frequency t 0 Hz Set frequency REV Run enable Ctrl signal 1 Ctrl signal 2 Keypad stop button 1 2 3 4 5 6 7 8 9 9176.emf Figure 16. I/O A Start/Stop logic = 1. Explanations: 1 Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward.
Siemens Application Selection number Siemens Industry, Inc. • 75 Selection name Note Used to exclude the possibility of an unintentional start. The Start/Stop contact must be opened before the motor can be restarted. CS1: Forward (edge) CS2: Backward (edge) 2 FWD Output frequency Set frequency t 0 Hz Set frequency REV Run enable Ctrl signal 1 Ctrl signal 2 Keypad stop button 1 2 3 4 5 6 7 8 9 10 11 12 11093.emf Figure 17. I/O A Start/Stop logic = 2.
Siemens Industry, Inc. • 76 Selection number Siemens Application Selection name Note CS1: Start CS2: Reverse 3 FWD Output frequency Set frequency t 0 Hz Set frequency REV Run enable Ctrl signal 1 Ctrl signal 2 Keypad start button Keypad stop button 1 2 3 4 6 7 8 9 10 11 12 5 11094.emf Figure 18. I/O A Start/Stop logic = 3. Explanations: 1 Control signal (CS) 1 activates causing the output frequency to rise. The motor runs forward.
Siemens Application Selection number Siemens Industry, Inc. • 77 Selection name Note Used to exclude the possibility of an unintentional start. The Start/Stop contact must be opened before the motor can be restarted. CS1: Start (edge) CS2: Reverse 4 FWD Output frequency Set frequency t 0 Hz Set frequency REV Run enable Ctr l signal 1 Ctr l signal 2 Keypad stop button 1 2 3 4 6 7 8 9 10 11 5 11095.emf Figure 19. I/O A Start/Stop logic = 4.
Siemens Industry, Inc. • 78 Selection number Siemens Application Selection name Note Combine activated inputs according to Table to choose the Preset frequency needed. 0 Binary coded 1 You can apply the Preset frequencies 1 to 3, depending on how Number (of inputs used) many of the inputs assigned for Preset frequency selections are active. Preset frequencies 1 to 7 (P3.3.11 to P3.3.18) The values of the preset frequencies are automatically limited between the minimum and maximum frequencies (P3.3.
Siemens Application Siemens Industry, Inc. • 79 [Hz] P3.4.2, P3.4.3 P3.4.1 P3.4.1 [t] 11096.emf Figure 20. Acceleration/Deceleration (S-shaped). Flux braking (P3.4.12) Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases where additional brake resistors are not needed. When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases the motor's capability to brake.
Siemens Industry, Inc. • 80 Siemens Application NOTE: Long filtering time makes the regulation response slower! % Unfiltered signal 100% Filtered signal 63% t [s] P3.5.2.2 11097.emf Figure 21. AI1 signal filtering. Basic R01 function (P3.5.3.2.1) Table 56. Output signals via RO1.
Siemens Application Siemens Industry, Inc. • 81 Table 56. Output signals via RO1. Selection Selection name Description 24 Reserved 25 PID1 supervision limits 26 PID2 supervision limits PID2 feedback value is beyond supervision limits. 27 Motor 1 control Contactor control for Multi-pump function PID1 feedback value is beyond supervision limits.
Siemens Industry, Inc. • 82 Siemens Application Motor thermal time constant (P3.9.9) The time constant is the time within which the calculated thermal stage has reached 63% of its final value. The bigger the frame and/or the slower the speed of the motor, the longer the time constant. The motor thermal time is specific to the motor design and it varies between different motor manufacturers. The default value of the parameter varies from size to size.
Siemens Application Siemens Industry, Inc. • 83 I Stall area Par. P3.9.12 f Par. P3.9.14 11100.emf Figure 24. Stall characteristics settings. Stall time limit (P3.9.13) This time can be set between 1.0 and 120.0s. This is the maximum time allowed for a stall stage. The stall time is counted by an internal up/down counter. If the stall time counter value goes above this limit, the protection will cause a trip (see P3.9.11). See page 49. Stall time counter Trip area Par. P3.9.13 Trip/warning par.
Siemens Industry, Inc. • 84 Siemens Application Torque Par. P3.9.16 Par. P3.9.17 Under load area f 5 Hz Fieldweakening point 11102.emf Figure 26. Setting of minimum load. Underload protection: Time limit (P3.9.18) This time can be set between 2.0 and 600.0 s. This is the maximum time allowed for an underload state to exist. An internal up/down counter counts the accumulated underload time.
Siemens Application Siemens Industry, Inc. • 85 Wait time (P3.10.3) Automatic reset: Trial time (P3.10.4) Number of trials (P3.10.5) The Automatic reset function keeps resetting the faults appearing during the time set with this parameter. If the number of faults during the trial time exceed the value of parameter P3.10.5, a permanent fault is generated. Otherwise the fault is cleared after the trial time has elapsed and the next fault starts the trial time count again. Parameter P3.10.
Siemens Industry, Inc. • 86 Siemens Application Dead band (P3.12.1.9) Reference Actual value Dead band delay (P3.12.1.10) Output locked 11105.emf Figure 29. Dead band. Sleep frequency limit 1 (P3.12.2.7) Sleep delay 1 (P3.12.2.8) Wake-up level 1 (P3.12.2.9) This function will put the drive into sleep mode if the frequency stays below the sleep limit for a longer period than that set with the Sleep Delay (P3.12.2.8). This means that the start command remains on, but the run request is turned off.
Siemens Application Siemens Industry, Inc. • 87 Feedforward function (P3.12.4.1) Feedforward usually needs accurate process models, but in some cases, a gain + offset type of feedforward is enough. The feedforward part does not use any feedback measurements of the actual controlled process value (water level in the example on page 87). Siemens feedforward control uses other measurements which are indirectly affecting the controlled process value.
Siemens Industry, Inc. • 88 Siemens Application Enable process supervision (P3.12.5.1) Actual value Upper limit P3.12.5.2) Refer ence Lower limit (P3.12.5.3) Delay (P3.12.5.4) Alarm or fault Regulating mode 11108.emf Figure 32. Process supervision. Upper and lower limits around the reference are set. When the actual value goes above or below, a counter starts counting up towards the Delay (P3.12.5.4). When the actual value is within the allowed area, the same counter counts down instead.
Siemens Application Siemens Industry, Inc. • 89 Enable setpoint 1 (P3.12.6.1) Setpoint 1 max compensation (P3.12.6.2) The sensor is placed in Position 1. The pressure in the pipe will remain constant when we have no flow. However, with flow, the pressure will drop farther down in the pipe. This can be compensated by raising the setpoint as the flow increases. In this case, the flow is estimated by the output frequency and the setpoint is linearly increased with the flow as in the figure below.
Siemens Industry, Inc. • 90 Siemens Application MULTI-PUMP USE Motors are connected/disconnected if the PID controller is not able to keep the process value or feedback within the defined bandwidth around the setpoint. Criteria for connecting/adding motors (also see Figure 35): • • • • Feedback value outside the bandwidth area. Regulating motor running at a “close-to-max” frequency (-2Hz). Conditions above are fulfilled for a time longer than the bandwidth delay. There are additional motors available.
Siemens Application Siemens Industry, Inc. • 91 EXAMPLE OF THE INTERLOCK LOGIC: If the motor starting order is 1->2->3->4->5 When the interlock of motor 3 is removed, i.e. the value of parameter P3.5.1.27 is set to FALSE, the order changes to: 1->2->4->5. If motor 3 is taken into use again (changing the value of parameter P3.5.1.
Siemens Industry, Inc. • 92 Siemens Application Figure 36. Selection 1, Enabled: If the regulating motor needs to be included in the auto-change or interlock logic make the connection according to Figure 37 below. Each motor is controlled by a relay, but the contact logic ensures that the first connected motor is always connected to the drive and near the mains.
Siemens Application Siemens Industry, Inc. • 93 Figure 37. Auto-change (P3.14.4) Selection 0 Selection name Disabled 24-hour support +1-800-877-7545 (Dial 2) Description The priority/starting order of the motors is always 1-2-3-4-5 in normal operation. It may have changed during its run if interlocks have been removed and added again, but the priority/ order is always restored after a stop.
Siemens Industry, Inc. • 94 Selection 1 Siemens Application Selection name Enabled Description The priority is changed at certain intervals to get an equal wear on all motors. The intervals of the auto-change can be changed (P3.14.5). You can also set a limit for how many motors are allowed to run (P3.14.7) as well as for the maximum frequency of the regulating drive when the auto-change is done (P3.14.6). If the auto-change interval P3.14.
Siemens Application 3.7.1 Siemens Industry, Inc. • 95 Fault appears When a fault appears and the drive stops, examine the cause of the fault, perform the actions advised here and reset the fault as instructed below. 1. Press the Reset button on the keypad for one second or 2. By entering the Diagnostics Menu (M4), entering Reset faults (M4.2) and selecting Reset faults parameter. READY I/O STOP READY ID: M4 Monitor ( 5 ) Parameters ( 12 ) Diagnostics ( 6 ) 3.7.
Siemens Industry, Inc. • 96 3.7.3 Siemens Application Fault codes Table 57. Fault codes and descriptions. Fault code Fault ID 1 Over-current (hardware fault) 2 Over-current (software fault) 10 Over-voltage (hardware fault) 11 Over-voltage (software fault) 1 2 20 3 21 5 7 Fault name 40 60 Possible cause Remedy The drive has detected too high a current (>4*IH) in the motor cable: • sudden heavy load increase • short circuit in motor cables • unsuitable motor Check loading. Check motor.
Siemens Application Siemens Industry, Inc. • 97 Table 57. Fault codes and descriptions. Fault code Fault ID Fault name Possible cause 600 Communication between control board and power unit has failed. 602 Watchdog has reset the CPU. Remedy Voltage of auxiliary power in power unit is Reset the fault and restart. Should the fault re-occur, contact too low. your distributor. Phase fault: Voltage of an output phase does not follow the reference.
Siemens Industry, Inc. • 98 Siemens Application Table 57. Fault codes and descriptions. Fault code Fault ID 130 131 14 132 Fault name Possible cause Remedy AC drive overtemperature (fault, heatsink) AC drive overtemperature (alarm, heatsink) Too high temperature measured in power unit’s heatsink or board. Heatsink temAC drive overperature is over 100 °C (212 °F). temperature (fault, board) Check the correct amount and flow of cooling air. Check the heatsink for dust. Check the ambient temperature.
Siemens Application Siemens Industry, Inc. • 99 Table 57. Fault codes and descriptions. Fault code Fault ID 44 430 Device changed (different type) Option board changed for one not present Set the option board parameters in the same slot before. No parameter setagain. tings are saved. 45 440 Device changed (different type) Option board added. The option board was not previously present in the same slot. No parameter settings are saved. 51 1051 External fault Digital input.
Siemens Industry, Inc.