User Manual

11
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
4.3.3 Semantics
The semantics describe the valid contents and significance of the fields within the con-
figuration file.
RecordNr
This field contains the line number of the entry in the configuration file.
RecordType
This field contains the type of entry. Currently the following record types have been de-
fined:
1 = Record1
2 = Record2 (corresponds to Record1 + fire department site plan number
+ intervention text)
SeqNr
This field contains the sequence number (unique key in the database of a CS11 sta-
tion) of the datapoint. If this field contains a value of 0, no instance of this datapoint ex-
ists. In this case this entry is used only for structural purposes.
StrucNr
This field contains the structure number (datatype) of the datapoint.
ParentSeqNr
This field contains the sequence number of the parent node of this datapoint.
TLSeqNr
TreeLinkSeqNr. This field contains the sequence number of the datapoint in the
opposite tree. Within the element entry the TLSeqNr refers to the corresponding device.
Within a device entry the TLSeqNr refers to the corresponding element.
CSXLevel
This field identifies the hierarchical level assigned to the datapoint. The following en-
tries are valid:
AREA Area
SECT Section
ZONE Zone
ELEM Element
DBD Device
IBD Function unit
CBD Station
Text1
This field contains the first part of the textual description for this datapoint. For data-
points within the logical tree it contains the description of the geographical/logical in-
formation. For datapoints within the physical tree it contains the description of the tech-
nical (hardware) information.
Text2
This field contains the second part of the textual description for this datapoint. For
datapoints within the logical tree it contains the description of the geographical/logical
information. For datapoints within the physical tree it contains the description of the
technical (hardware) information.
DMSSector
This field describes the affiliated danger sector. Valid entries are:
A = Fire
B = Extinguishing
C = Intrusion
D = Gas
E = Plant monitoring
0 (Null) = Basic sector
X = Dummy entry. The whole record does not provide datapoints and is
for structure purposes only