User Manual

12
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
DMSAdf12
This field contains the ADF1/2 number which is derived from the SeqNr. From the
viewpoint of the DMS7000 the ADV1/2 number is the address of the CC11 datapoint.
This number is the primary key for assigning process information (telegrams) to struc-
ture information (configuration file).
Attribute
This field contains StrucNr-dependent specifics. If no specifics are needed this field
contains a dash (“-”).
StrucNr = 1562 (Remote transmission channel)
The attribute defines the utilization of the remote transmission channel. Valid entries
are:
RTFIRE Remote transmission channel ALARM
RTFAULT Remote transmission channel FAULT
RTOTHER Remote transmission channel OTHER
StrucNr = 1201 (CC11 station)
The attribute defines the DMS7000 network address of the CC11 station. Valid entries:
nnn valid DMS7000 network address for control units, e.g. 111.
StrucNr = 1203 (CK11 station)
The attribute defines the DMS7000 network address of the CK11 station. Valid entries:
nnn valid DMS7000 network address for gateways, e.g. 860.
Layer
This field identifies the tree assigned to this datapoint. The layer information is used as
a prefix to the CSXNumber, because the latter is unique only within a tree. Valid en-
tries:
LOG Logical tree
PHYS Physical tree
RTDEV Assignment tree for remote transmission devices
RTREC Assignment tree for remote transmission channel
IHORN Assignment tree for internal horns
EHORN Assignment tree for external horns
??? Unknown assignment, error
CSXNumber
This field identifies the position of the node within a tree. Valid entries:
Log. tree Area:Section:Zone:Element Example: 001:003:087:009
Phys. tree CBD:IBD:DBD Example: 001:010:054
Invalid entries are marked with “???”
FplanNr
This field contains the number of the assigned fire department site plan. 0 = No site
plan available.
IntvTxtNr
This field contains the number of the corresponding action text. 0 = No text available