5.2 Hierarchical level: AREA
5.2.1 Structure 1801: FIRE area
Abstract representation of a FIRE area. The area contains the datapoints:
- ORGANIZATION
- GENERAL ALARM
- ALARM RT DELAY (RT = Remote transmission)
- PART OF SYSTEM OFF
- FAULT
- RT-DEVICE (datapoint formerly presented in structure 1563)
Datapoint ORGANIZATION (ORG)
This datapoint relates to the alarm organization (CAC) within the area.
1801/ORG: Addressing
Sector: FIRE
ADF1/2: aaEF(aa = “A” + <area number>, example: A1EF = Organization in area 1)
1801/ORG: Valid states
State Description Valid commands
MANNED
(Day mode)
The area operates in Day mode. When an alarm occurs external
intervention squads are summoned only after predefined delay
times (V1, V2) or systematic human action (pressing an manual
callpoint).
UNMANNED
UNMANNED
(Night mode)
The area operates in Night mode. When an alarm occurs external
intervention squads are summoned immediately.
MANNED
1801/ORG: State transition diagram
To
From
NIGHT MODE DAY MODE
NIGHT MODE
---
Day mode
--------------
N 55 61
DAY MODE Night mode
--------------
N 55 60
---
1801/ORG: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> N 55 60 ANOMALY Organization Night (Night mode)
W <CCaddr> <adf12> N 55 61 ANOMALY Organization Tag (Day mode)
1801/ORG: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <adf12> R 55 55 Organization On (Night mode)
W <CCaddr> <adf12> R 55 56 Organization Off (Day mode)