1701: Telegram repertoire COMMANDS (ZONE commands from SECTION level)
It is valid to use selected ZONE level commands on SECTION level. The command is
then propagated to ALL zones belonging to the respective section. These command
telegrams always contain the ADF1/2 of the respective section!
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <SECT-adf12> R 01 80 Alarm Acknowledgment (Alarm)
W <CCaddr> <SECT-adf12> R 01 83 Alarm Reset
W <CCaddr> <SECT-adf12> R 03 89 Warning Acknowledgment (Anomaly)
W <CCaddr> <SECT-adf12> R 64 3F Zone Revision
W <CCaddr> <SECT-adf12> R 64 55 Zone on
W <CCaddr> <SECT-adf12> R 64 56 Zone off
W <CCaddr> <SECT-adf12> R 64 57 Zone Test
5.3.2 Structure 1702: EXTINGUISHING section
The EXTINGUISHING section represents the state of the extinguishing control for an
extinguishing section. The following datapoints are offered:
- EXTINGUISHING
- RELEASE
- FAULT
Datapoint EXTINGUISHING (EAL)
This datapoint contains the alarm information of the corresponding extinguishing sec-
tion.
1702/EAL: Addressing
Sector: EXTINGUISHING
ADF1/2: bbEB (bb = “B” + <IBus number Extinguishing module>,
example: B5EB = alarm in section 5)
i
On the DMS7000 side the CSX number cannot be used for addressing the extinguish-
ing section because its number range (1..99) is too large. For this reason the IBUS
number of the affiliated extinguishing module (Hex 0..F) is used for addressing.
The CSX number of the extinguishing section can be found in the configuration file.
1702/EAL: Valid states
State Description Valid commands
RESET The section is not in the alarm state.
EXTING. ALARM
MAN. ACTIVATION
The extinguishing system has been activated manually, that is,
without an extinguishing command of the CC11.
ACKNOWLEDGE
RESET
EXTING. ALARM
AUTOM. DETEC-
TOR
An affiliated extinguishing zone has transmitted an extinguishing
command to the section. At this point the extinguishing sequence is
started and can only be interrupted by pressing the Stop button
(within the specified time).
ACKNOWLEDGE
RESET
EXTING: ALARM
MAN. DETECTOR
The extinguishing button has been actuated. At this point the
extinguishing sequence is started and can only be interrupted by
pressing the Stop button (within the specified time).
ACKNOWLEDGE
RESET