1702: Telegram repertoire COMMANDS (ZONE commands from SECTION level)
It is valid to use selected ZONE level commands on SECTION level. The command is
then propagated to ALL zones belonging to the respective section. These command
telegrams always contain the ADF1/2 of the respective section!
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
L <CCaddr> <SECT-adf12> R 03 89 Warning Acknowledgment (Anomaly)
L <CCaddr> <SECT-adf12> R 04 80 Alarm Acknowledgment (Alarm)
L <CCaddr> <SECT-adf12> R 04 83 Alarm Reset
L <CCaddr> <SECT-adf12> R 08 80 Alarm Acknowledgment (Alarm)
L <CCaddr> <SECT-adf12> R 08 83 Alarm Reset
L <CCaddr> <SECT-adf12> R 64 3F Zone Revision
L <CCaddr> <SECT-adf12> R 64 55 Zone on
L <CCaddr> <SECT-adf12> R 64 56 Zone off
L <CCaddr> <SECT-adf12> R 64 57 Zone Test
Datapoint: FAULT (FLT)
This datapoint becomes active if one or more faults exist in the corresponding extin-
guishing section.
1702/FLT: Addressing
Sector: EXTINGUISHING
ADF1/2: bbED (bb = “B” + <I-Bus number Extinguishing module>,
example: B6ED = Release in section 6)
1702/FLT: Valid states
State Description Valid commands
INACTIVE No fault in the corresponding extinguishing section. ---
ACTIVE Faults exist in the corresponding extinguishing section. Causes:
- Loss of extinguishing agent
- Broken glass of manual callpoint
- Faulty “Extinguishing valve”, “Control device”, “Extinguishing
agent”, “Manual release button”, “Emergency stop/Inhibit”,
“Warning horn” or “Warning beacon”
- Extinguishing system not ready (valve active but no extinguish-
ing agent available)
ACKNOWLEDGE
1702/FLT: State transition diagram
To
From
ACTIVE INACTIVE
ACTIVE
---
Active
--------------
N 3A 3B
INACTIVE Active
--------------
U 3A 3A
---
1702/FLT: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
L <CCaddr> <adf12> U/Q 3A 3A FAULT Fault ---
L <CCaddr> <adf12> N 3A 3B NORMAL Fault End
1702/FLT: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
L <CCaddr> <adf12> R 3A 86 Fault Acknowledgment