1601: State transition diagram
To
From
WARNING ALARM OFF TEST REVISION RENOVATION NOT READY NORMAL
WARNING
---
Alarm
----------------
N 03 3B
U 01 01
Off
--------------
N 03 3B
Q 64 56
Test
--------------
N 03 3B
Q 64 57
WARNING
&
mode = Revis.
-----------------
N 03 3B
N 64 3F
WARNING
&
mode = Reno.
-----------------
N 03 3B
N 64 3E
---
WARNING
-----------------
N 03 3B
N 64 3C
ALARM
--- ---
Off
--------------
N 01 85
Q 64 56
Test
--------------
N 01 85
Q 64 57
Reset &
mode = Revis.
-----------------
N 01 85
N 64 3F
Reset &
mode = Reno.
-----------------
N 01 85
N 64 3E
---
Reset &
Danger = 0
--------------
N 01 85
N 64 3C
OFF
--- --- ---
Test
--------------
Q 64 57
--- ---
On & Danger
> 2
-----------------
Q 64 5F
On
--------------
N 64 3C
TEST
--- ---
Off
--------------
Q 64 56
--- --- ---
On & Danger
> 2
-----------------
Q 64 5F
On
--------------
N 64 3C
REVISION WARNING
-----------------
U 03 3A
Alarm
----------------
U 01 01
Off
--------------
Q 64 56
Test
--------------
Q 64 57
---
Renov.
--------------
Q 64 3E
---
On
--------------
N 64 3C
RENOVA-
TION
WARNING
-----------------U
03 3A
Alarm
----------------
U 01 01
Off
--------------
Q 64 56
Test
--------------
Q 64 57
Revision
--------------
Q 64 3F
--- ---
On
--------------
N 64 3C
NOT READY
--- ---
Off
--------------
Q 64 56
Test
--------------
Q 64 57
--- --- ---
On
--------------
N 64 3C
NORMAL WARNING
-----------------U
03 3A
Alarm
----------------
U 01 01
Off
--------------
Q 64 56
Test
--------------
Q 64 57
Revision
--------------
Q 64 3F
Renov.
--------------
Q 64 3E
--- ---
1601: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> U/Q 01 01 ALARM Alarm Autom. detector
W <CCaddr> <adf12> N 01 85 NORMAL Alarm Reset
W <CCaddr> <adf12> U/Q 03 3A ANOMALY WARNING ---
W <CCaddr> <adf12> N 03 3B NORMAL WARNING End
W <CCaddr> <adf12> Q 64 3E ANOMALY Zone Renovation
W <CCaddr> <adf12> Q 64 3F ANOMALY Zone Revision
W <CCaddr> <adf12> Q 64 56 ANOMALY Zone Off
W <CCaddr> <adf12> Q 64 57 ANOMALY Zone Test
W <CCaddr> <adf12> Q 64 5F ANOMALY Zone Not ready
W <CCaddr> <adf12> N 64 3C NORMAL Zone Normal
1601: Telegram repertoire: COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <adf12> R 01 80 Alarm Acknowledgment (Alarm)
W <CCaddr> <adf12> R 01 83 Alarm Reset
W <CCaddr> <adf12> R 03 89 WARNING Acknowledgment (anomaly)
W <CCaddr> <adf12> R 03 8D
1
WARNING Reset (anomaly)
W <CCaddr> <adf12> R 64 3E Zone Renovation
W <CCaddr> <adf12> R 64 3F Zone Revision
W <CCaddr> <adf12> R 64 55 Zone On
W <CCaddr> <adf12> R 64 56 Zone Off
W <CCaddr> <adf12> R 64 57 Zone Test
1