1602/B: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
L <CCaddr> <adf12> U/Q 03 3A ANOMALY Warning ---
L <CCaddr> <adf12> N 03 3B NORMAL Warning End
L <CCaddr> <adf12> U/Q 04 01 ALARM Pre-alarm Autom. detector
L <CCaddr> <adf12> N 04 85 NORMAL Pre-alarm Reset
L <CCaddr> <adf12> U/Q 08 01 ALARM Extinguishing alarm Autom. detector
L <CCaddr> <adf12> N 08 85 NORMAL Extinguishing alarm Reset
L <CCaddr> <adf12> Q 64 3E ANOMALY Zone Renovation
L <CCaddr> <adf12> Q 64 3F ANOMALY Zone Revision
L <CCaddr> <adf12> Q 64 56 ANOMALY Zone Off
L <CCaddr> <adf12> Q 64 57 ANOMALY Zone Test
L <CCaddr> <adf12> Q 64 5F ANOMALY Zone Not ready
L <CCaddr> <adf12> N 64 3C NORMAL Zone Normal
1602/B: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
L <CCaddr> <adf12> R 03 89 Warning Acknowledgment (anomaly)
L <CCaddr> <adf12> R 03 8D
5
Warning Reset (anomaly)
L <CCaddr> <adf12> R 04 80 Pre-alarm Acknowledgment (Alarm)
L <CCaddr> <adf12> R 04 83 Pre-alarm Reset
L <CCaddr> <adf12> R 08 80 Extinguishing alarm Acknowledgment (Alarm)
L <CCaddr> <adf12> R 08 83 Extinguishing alarm Reset
L <CCaddr> <adf12> R 64 3E Zone Renovation
L <CCaddr> <adf12> R 64 3F Zone Revision
L <CCaddr> <adf12> R 64 55 Zone On
L <CCaddr> <adf12> R 64 56 Zone Off
L <CCaddr> <adf12> R 64 57 Zone Test
5
Only applicable if the “Warning” state has been defined as resettable in the CC11 configuration.