5.5.4 Structure 1605: Manual callpoint zone
In a manual callpoint zone only one detection device assigned to the zone needs to re-
spond in order to reach the ALARM state.
1605: Addressing
Sector: FIRE
ADF1/2: Based on sequence number
1605: Valid states
State Description Valid commands
NORMAL The zone is in the ON state. Incoming danger levels are processed. OFF
TEST
ALARM An affiliated detection device has reached danger level 3 (alarm). ACKNOWLEDGE
RESET
OFF
TEST
OFF Incoming danger levels are not processed.
Note:
If all elements affiliated with the zone are switched off, the state of
the zone switches automatically to OFF.
ON
TEST
TEST Incoming danger levels are not processed. The responding detec-
tion device switches temporarily to the TEST ALARM state.
ON
OFF
NOT READY A pending danger level (manual button) has been detected when
the zone was switched on.
OFF
TEST
1605: State transition diagram
To
From
ALARM OFF TEST NOT READY NORMAL
ALARM
---
Off
--------------
N 01 85
Q 64 56
Test
--------------
N 01 85
Q 64 57
---
Reset & Danger = 0
--------------
N 01 85
N 64 3C
OFF
--- ---
Test
--------------
Q 64 57
On & Danger > 0
-----------------
Q 64 5F
On
--------------
N 64 3C
TEST
---
Off
--------------
Q 64 56
---
On & Danger > 0
-----------------
Q 64 5F
On
--------------
N 64 3C
NOT READY
---
Off
--------------
Q 64 56
Test
--------------
Q 64 57
---
On
--------------
N 64 3C
NORMAL Alarm
----------------
U 01 02
Off
--------------
Q 64 56
Test
--------------
Q 64 57
--- ---
1605: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> U/Q 01 02 ALARM Alarm Man. detector
W <CCaddr> <adf12> N 01 85 NORMAL Alarm Reset
W <CCaddr> <adf12> Q 64 56 ANOMALY Zone Off
W <CCaddr> <adf12> Q 64 57 ANOMALY Zone Test
W <CCaddr> <adf12> Q 64 5F ANOMALY Zone Not ready
W <CCaddr> <adf12> N 64 3C NORMAL Zone Normal