User Manual

36
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
1610: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
LP <CCaddr> <adf12> U/Q 01 01 ALARM Alarm Autom. detector
LP <CCaddr> <adf12> N 01 85 NORMAL Alarm Reset
LP <CCaddr> <adf12> Q 64 56 ANOMALY Zone Off
LP <CCaddr> <adf12> Q 64 57 ANOMALY Zone Test
LP <CCaddr> <adf12> Q 64 5F ANOMALY Zone Not ready
LP <CCaddr> <adf12> N 64 3C NORMAL Zone Normal
1610: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
LP <CCaddr> <adf12> R 01 80 Alarm Acknowledgment (Alarm)
LP <CCaddr> <adf12> R 01 83 Alarm Reset
LP <CCaddr> <adf12> R 64 55 Zone On
LP <CCaddr> <adf12> R 64 56 Zone Off
LP <CCaddr> <adf12> R 64 57 Zone Test
5.6 Hierarchical level: ZONE (controls)
The CONTROL ZONE level is responsible for activating the affiliated control elements
based on predetermined decision criteria. The term ‘Zone’ (controls) corresponds to the
term Control zone in the DMS7000.
5.6.1 Structure 1651: Switching zone
Based on the evaluation of the affiliated digital detection devices the affiliated control
elements are activated. This zone type is principally used in the local area of the CC11.
1651: Addressing
Sector: PLANT MONITORING
ADF1/2: Based on sequence number
1651: Valid states
State Description Valid commands
INACTIVE
The zone is in the quiescent state. The evaluation logic is switched on. OFF
OFF
The evaluation logic is switched off. The affiliated elements are deacti-
vated.
ON
FAULTY
Zone faulty. The affiliated elements are deactivated. ACKNOWLEDGE
1651: State transition diagram
To
From
OFF FAULTY INACTIVE
OFF
---
Fault
--------------
U 62 46
On
--------------
N 62 4D
FAULTY
--- ---
Fault
--------------
U 62 4D
INACTIVE Off
--------------
Q 62 56
Fault
--------------
U 62 46
---