User Manual

41
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
5.7.3 Structure 1503: Collective manual callpoint element
Abstract representation of a collective series DS11-C manual callpoint.
1503: Addressing
Sector: FIRE
ADF1/2: Based on sequence number
1503: Valid states
State Description Valid commands
NORMAL
The element is in the ON state (connected to the circuit). Incoming
danger levels are transmitted to the higher ranking zone.
OFF
ACTIVE
The affiliated detector has reached a danger level > 1. OFF
TEST ALARM
The higher ranking zone is in the TEST state and a danger level 3
has been detected.
OFF
OFF
Incoming information (danger levels, faults) is not processed. ON
NOT READY
After the element has been reset or switched on a pending danger
level (push button engaged) was detected.
ACKNOWLEDGE
OFF
FAULTY
Correct functioning of the detector is no longer assured. Causes:
- Fatal fault (interruption, short circuit, HW)
ACKNOWLEDGE
OFF
1503: State transition diagram
To
From
ACTIVE OFF TEST ALARM
ZONE = TEST
NOT READY FAULTY NORMAL
ACTIVE
---
Off
--------------
Q 67 56
--- ---
Active &
Faulty
--------------
U 67 46
ZoneReset &
Danger = 0
--------------
N 67 3C
OFF
--- --- ---
On &
Not ready
--------------
U 67 5F
On &
Faulty
--------------
U 67 46
On
--------------
N 67 3C
TEST ALARM
ZONE = TEST
---
Off
--------------
Q 67 56
--- --- ---
TestAlarm
-------------
N 67 3C
NOT READY
---
Off
--------------
Q 67 56
--- --- ---
Danger = 0
-----------------
N 67 3C
FAULTY
---
Off
--------------
Q 67 56
--- --- ---
Faulty
-------------
N 67 3C
NORMAL Danger = 3
--------------
Q 67 4F
Off
--------------
Q 67 56
Danger = 3
--------------
Q 67 0B
N.ready
--------------
U 67 5F
Faulty
--------------
U 67 46
---
1503: Telegram repertoire: MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> Q 67 0B ANOMALY Detection device Test alarm
W <CCaddr> <adf12> N 67 3C NORMAL Detection device Normal
W <CCaddr> <adf12> U/Q 67 46 FAULT Detection device Faulty
W <CCaddr> <adf12> Q 67 4F ANOMALY Detection device Active
W <CCaddr> <adf12> Q 67 56 ANOMALY Detection device Off
W <CCaddr> <adf12> U/Q 67 5F FAULT Detection device Not ready
1503: Telegram repertoire: COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <adf12> R 67 55 Detection device On
W <CCaddr> <adf12> R 67 56 Detection device Off
W <CCaddr> <adf12> R 67 86 Detection device Acknowledgment (fault)