User Manual

43
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
5.7.5 Structure 1510...1512: Collective line element
Abstract representation of a series DS11-C collective line. Elements 1510 .. 1512 have
different internal characteristics (pulse memory, delays), however, these do not appear
on the DMS7000 side.
1510: Addressing
Sector: FIRE or EXTINGUISHING
ADF1/2: Based on sequence number
1510: Valid states
State Description Valid commands
NORMAL
The element is in the ON state (connected to the circuit). Incoming
danger levels are transmitted to the higher ranking zone.
OFF
ACTIVE
The affiliated detector has reached a danger level > 1. OFF
TEST ALARM
The higher ranking zone is in the TEST state and a danger level 3
has been detected.
OFF
OFF
Incoming information (danger levels, faults) is not processed. ON
DRIFT
Detector contaminated but still functional. ACKNOWLEDGE
OFF
FAULTY
Correct functioning of the detector is no longer assured. Causes:
- Fatal fault (detector HW)
- Detector line faulty
ACKNOWLEDGE
OFF
1510: State transition diagram
To
From
ACTIVE OFF TEST ALARM
ZONE = TEST
DRIFT FAULTY NORMAL
ACTIVE
---
Off
--------------
Q 67 56
---
Active &
Drift
-------------
U 67 48
Active &
Faulty
--------------
U 67 46
ZoneReset &
Danger = 0
--------------
N 67 3C
OFF
--- --- ---
On &
Drift
--------------
U 67 48
On &
Faulty
--------------
U 67 46
On
--------------
N 67 3C
TEST ALARM
ZONE = TEST
---
Off
--------------
Q 67 56
---
TestAlarm & Drift
-------------
U 67 48
---
TestAlarm
-------------
N 67 3C
DRIFT Danger > 1
--------------
Q 67 4F
Off
--------------
Q 67 56
Danger = 3
--------------
Q 67 0B
--- ---
Drift
-------------
N 67 3C
FAULTY
---
Off
--------------
Q 67 56
---
Faulty & Drift
-------------
U 67 48
---
Faulty
-------------
N 67 3C
NORMAL Danger > 1
--------------
Q 67 4F
Off
--------------
Q 67 56
Danger = 3
--------------
Q 67 0B
Drift
--------------
U 67 48
Faulty
--------------
U 67 46
---
1510: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
WL <CCaddr> <adf12> Q 67 0B ANOMALY Detection device Test alarm
WL <CCaddr> <adf12> N 67 3C NORMAL Detection device Normal
WL <CCaddr> <adf12> U/Q 67 46 FAULT Detection device Faulty
WL <CCaddr> <adf12> U/Q 67 48 ANOMALY Detection device Drift
WL <CCaddr> <adf12> Q 67 4F ANOMALY Detection device Active
WL <CCaddr> <adf12> Q 67 56 ANOMALY Detection device Off
1510: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
WL <CCaddr> <adf12> R 67 55 Detection device On
WL <CCaddr> <adf12> R 67 56 Detection device Off
WL <CCaddr> <adf12> R 67 86 Detection device Acknowledgment (fault)
WL <CCaddr> <adf12> R 67 89 Detection device Acknowledgment (anomaly)