User Manual

52
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
1561: State transition diagram
To
From
ACTIVE OFF FAULTY INACTIVE
ACTIVE
---
Off
--------------
Q 73 56
Active &
Faulty
--------------
U 73 46
Inactive
--------------
N 73 4D
OFF
--- ---
On &
Faulty
--------------
U 73 46
On
--------------
N 73 4D
FAULTY
---
Off
--------------
Q 73 56
---
Faulty
-------------
N 73 4D
INACTIVE Active
--------------
U 73 4F
Off
--------------
Q 73 56
Faulty
--------------
U 73 46
---
1561: Telegram repertoire: MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> U/Q 73 46 FAULT External horn Faulty
W <CCaddr> <adf12> N 73 4D NORMAL External horn Inactive
W <CCaddr> <adf12> U/Q 73 4F ANOMALY External horn Active
W <CCaddr> <adf12> Q 73 56 ANOMALY External horn Off
1561: Telegram repertoire Commands
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <adf12> R 73 4D External horn Inactive
W <CCaddr> <adf12> R 73 4F External horn Active
W <CCaddr> <adf12> R 73 55 External horn On
W <CCaddr> <adf12> R 73 56 External horn Off
W <CCaddr> <adf12> R 73 86 External horn Acknowledgment (fault)
W <CCaddr> <adf12> R 73 89 External horn Acknowledgment (anomaly)