5.9.3 Structure 1303: Function unit DS11-A Line
Abstract representation of an DS11-A (AnalogPlus). The function unit contains the two
datapoints ALARM and FAULT. The datapoints appear under the same ADF1/2 ad-
dress, but with different sector ID. Together this results in a unique datapoint address.
Datapoint ALARM (ALM)
1303/ALM: Addressing
Sector: FIRE
ADF1/2: Based on sequence number
1303/ALM: Valid states
State Description Valid commands
RESET
The function unit is not in the alarm state.
ALARM
Collective alarm. An unidentifiable detector has responded.
Causes:
- Detector installed but not configured in the system.
- Due to a fault the detector cannot be identified individually.
ACKNOWLEDGE
RESET
1303/ALM: State transition diagram
To
From
ALARM RESET
ALARM
---
Alarm
--------------
N 01 85
RESET Alarm
--------------
U 01 00
---
1303/ALM: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> U/Q 01 00 ALARM Alarm ---
W <CCaddr> <adf12> N 01 85 NORMAL Alarm Reset
1303/ALM: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <adf12> R 01 80 Alarm Acknowledgment (Alarm)
W <CCaddr> <adf12> R 01 83 Alarm Reset