User Manual

61
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
Datapoint FAULT (FLT)
1303/FLT: Addressing
Sector: BASIC
ADF1/2: Based on sequence number
1303/FLT: Valid states
State Description Valid commands
NORMAL
No fault in the function unit.
FAULTY
One of the following faults exists in the function unit:
- Processor failure
- Emergency operation monitoring defective
- Line faulty
- Line does not respond
- Configuration error
ACKNOWLEDGE
1303/FLT: State transition diagram
To
From
FAULTY NORMAL
FAULTY
---
Fault
--------------
N 34 3C
NORMAL Fault
--------------
U 34 46
---
1303/FLT: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
Z <CCaddr> <adf12> N 34 3C NORMAL Function unit Normal
Z <CCaddr> <adf12> U/Q 34 46 FAULT Function unit Faulty
1303/FLT: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
Z <CCaddr> <adf12> R 34 86 Function unit Acknowledgment (fault)