5.9.8 Structure 1391: Function unit FBA panel (CI11 only)
Abstract representation of a FBA panel (fire brigade control panel). This structure is
only visible in CI11 control panels.
1391: Addressing
Sector: BASIC
ADF1/2: Based on sequence number
1391: Valid states
State Description Valid commands
NORMAL
No fault in the function unit.
FAULTY
One of the following faults exists in the function unit:
- No connection to FBA
- General fault
ACKNOWLEDGE
1391: State transition diagram
To
From
FAULTY NORMAL
FAULTY
---
Fault
--------------
N 34 3C
NORMAL Fault
--------------
U 34 46
---
1391: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
Z <CCaddr> <adf12> N 34 3C NORMAL Function unit Normal
Z <CCaddr> <adf12> U/Q 34 46 FAULT Function unit Faulty
1391: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
Z <CCaddr> <adf12> R 34 86 Function unit Acknowledgment (fault)